1-56 U/f Characteristic - F
Range:
Function:
Motor Voltage
Par 1-55 [x]
Output Frequency
Par 1-56 [x]
1-55[5]
1-55[4]
1-55[3]
1-55[2]
1-55[1]
1-55[0]
1-56
[0]
1-56
[1]
1-56
[2]
1-56
[3]
1-56
[4]
1-56
[5]
130BA166.10
Illustration 4.3 Example of U/f Charac-
teristic
4.2.7 1-6* Load Depen. Setting
Parameters for adjusting the load-dependent motor
settings.
1-60 Low Speed Load Compensation
Range:
Function:
100 %
*
[0 -
300 %]
Enter the low-speed voltage compensation
value in percent. This parameter is used for
optimising the low-speed load performance.
This parameter is only active if
parameter 1-10 Motor Construction
=
[0]
Asynchron
.
1-61 High Speed Load Compensation
Range:
Function:
100 %
*
[0 -
300 %]
Enter the high-speed load voltage compen-
sation value in percent. This parameter is
used for optimising the high-speed load
performance. This parameter is only active if
parameter 1-10 Motor Construction
=
[0]
Asynchron
.
1-62 Slip Compensation
Range:
Function:
Size
related
*
[ -400 -
399.0 %]
Enter the % value for slip compensation
to compensate for tolerance in the
value of n
M,N
. Slip compensation is
calculated automatically, that is, based
on the nominal motor speed n
M,N
.
1-63 Slip Compensation Time Constant
Range:
Function:
0.1 s
*
[0.05 - 5 s] Enter the slip compensation reaction speed.
A high value results in slow reaction, and a
low value results in quick reaction. If low-
frequency resonance problems occur, use a
longer time setting.
1-64 Resonance Dampening
Range:
Function:
100
%
*
[0 -
500 %]
Enter the resonance dampening value. Set
parameter 1-64 Resonance Dampening
and
parameter 1-65 Resonance Dampening Time
Constant
to help eliminate high-frequency
resonance problems. To reduce resonance
oscillation, increase the value of
parameter 1-64 Resonance Dampening
1-65 Resonance Dampening Time Constant
Range:
Function:
0.005 s
*
[ 0.001 -
0.05 s]
Set
parameter 1-64 Resonance Dampening
and
parameter 1-65 Resonance Dampening
to help eliminate high-
frequency resonance problems. Enter the
time constant that provides the best
dampening.
1-66 Min. Current at Low Speed
Range:
Function:
50 %
*
[ 0 -
120 %]
Enter the minimum motor current at low speed,
see
parameter 1-53 Model Shift Frequency
.
Increasing this current improves motor torque at
low speed.
Parameter 1-66 Min. Current at Low Speed
is
enabled when
parameter 1-00 Configuration Mode
[0] Speed open loop
only. The frequency converter
runs with constant current through motor for
speeds below 10 Hz.
Parameter 4-16 Torque Limit Motor Mode
and/or
parameter 4-17 Torque Limit Generator Mode
automatically adjust
. The parameter with the highest
value adjusts
parameter 1-66 Min. Current at Low
. The current setting in
is composed of the torque
generating current and the magnetising current.
Example: Set
parameter 4-16 Torque Limit Motor
to 100% and set
to 60%.
automatically adjusts to
about 127%, depending on the motor size.
Parameter Descriptions
Programming Guide
MG06C602
Danfoss A/S © 7/2015 All rights reserved.
33
4
4