NOTE!
This parameter cannot be changed when the motor is running.
NOTE!
When set for closed-loop, the commands reversing and start reversing will not reverse the direction of the motor.
1-20 Motor Power [kW]
Range:
Function:
Application
dependent*
[Application dependant]
Enter the nominal motor power in kW according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. Depending on the choices made in
par. 0-03
Regional Settings
, either par. 1-20
or par. 1-21
Motor Power [HP]
is
made invisible.
1-22 Motor Voltage
Range:
Function:
Application
dependent*
[Application dependant]
Enter the nominal motor voltage according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
1-23 Motor Frequency
Range:
Function:
Application
dependent*
[20 - 1000 Hz]
Select the motor frequency value from the motor nameplate data.For 87 Hz operation with 230/400
V motors, set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
and par. 3-03
to the 87 Hz application.
NOTE!
This parameter cannot be adjusted while the motor is running.
1-24 Motor Current
Range:
Function:
Application
dependent*
[Application dependant]
Enter the nominal motor current value from the motor nameplate data. This data is used for cal-
culating motor torque, motor thermal protection, etc.
NOTE!
This parameter cannot be adjusted while the motor is running.
VLT AQUA Low Harmonic Drive Instruction
Manual
6 How to Program the Low Harmonic Drive
MG.20.T1.22 - VLT
®
is a registered Danfoss trademark
6-15