0-43 [Reset] Key on LCP
Option:
Function:
[0]
Disabled
Select to disable the key.
[1]
*
Enabled
[Reset] key is enabled.
[2]
Password
Avoid unauthorized resetting. If
parameter 0-43 [Reset] Key on LCP
is included
in
parameter 0-25 My Personal Menu
, define
the password in
. Otherwise, define the
password in
.
[3]
Enabled
without OFF
[4]
Password
without OFF
[5]
Enabled with
OFF
Pressing the key resets the frequency
converter, but does not start it.
[6]
Password
with OFF
Prevents unauthorized reset. After authorized
reset, the frequency converter does not
start. See option
[2] Password
for information
on how to set the password.
0-44 [Off/Reset] Key on LCP
Enable or disable the [Off/Reset] key.
Option:
Function:
[0]
Disabled
[1]
*
Enabled
[2]
Password
0-45 [Drive Bypass] Key on LCP
Press [Off] and select
[0] Disabled
to avoid unintended stop of
the frequency converter. Press [Off] and select
[2] Password
to
avoid unauthorized bypass of the frequency converter. If
parameter 0-45 [Drive Bypass] Key on LCP
is included in the
Quick
Menu
, define the password in
Option:
Function:
[0]
Disabled
Select to disable the
key.
[1]
*
Enabled
[2]
Password
3.2.6 0-5* Copy/Save
Copy parameters from and to the LCP. Use these
parameters for saving and copying set-ups from 1
frequency converter to another.
0-50 LCP Copy
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
[0]
*
No copy
[1]
All to LCP
Copies all parameters in all set-ups from the
frequency converter memory to the LCP
memory. For service purposes, copy all
parameters to the LCP after commissioning.
[2]
All from LCP Copies all parameters in all set-ups from the
LCP memory to the frequency converter
memory.
[3]
Size indep.
from LCP
Copies only the parameters that are
independent of the motor size. Use the latest
selection to program several frequency
converters with the same function without
disturbing motor data which is already set.
[10] Delete LCP
copy data
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function.
[1]
Copy to
set-up 1
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
) to set-up 1.
[2]
Copy to
set-up 2
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
) to set-up 2.
[3]
Copy to
set-up 3
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
) to set-up 3.
[4]
Copy to
set-up 4
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
) to set-up 4.
[9]
Copy to
all
Copies the parameters in the present set-up to
each of the set-ups 1 to 4.
Parameter Description
VLT
®
AQUA Drive FC 202
36
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3
Содержание VLT AQUA Drive FC 202
Страница 2: ......