WARNING 250, New spare part
A component in the adjustable frequency drive has been
replaced.
Troubleshooting
•
Reset the adjustable frequency drive for normal
operation.
WARNING 251, New typecode
The power card or other components have been replaced
and the type code has been changed.
Troubleshooting
•
Reset to remove the warning and resume normal
operation.
7.4 Warning and Alarm Definitions - Filter (Left LCP)
NOTICE!
This section covers warnings and alarms on the filter side LCP. For warning and alarms for the adjustable frequency
drive, see
chapter 7.3 Warnings and Alarm Definitions - Adjustable Frequency Drive
A warning or an alarm is signaled by the relevant LED on the front of the filter and indicated by a code on the display. A
warning remains active until its cause is no longer present. Under certain circumstances, operation of the unit may still be
continued. Warning messages may be critical, but are not necessarily so. In the event of an alarm, the unit will have tripped.
Alarms must be reset to restart operation once their cause has been rectified.
This may be done in four ways:
1.
By pressing [Reset].
2.
Via a digital input with the “Reset” function.
3.
Via serial communication/optional serial communication bus.
4.
By resetting automatically using the [Auto Reset] function.
NOTICE!
After a manual reset pressing [Reset], press [Auto On] or [Hand On] to restart the unit.
If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked (see also
). Alarms that are trip-locked offer additional protection, meaning that the line power supply must be switched off
before the alarm can be reset. After being switched back on, the unit is no longer blocked and may be reset as described
above once the cause has been rectified.
Alarms that are not trip-locked can also be reset using the automatic reset function in
parameter 14-20 Reset Mode
(Warning:
automatic wake-up is possible). If a warning and alarm is marked against a code in
, either a warning occurs before
an alarm, or it can be specified whether it is a warning or an alarm that is to be displayed for a given fault.
No.
Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter Reference
1
10 Volts low
X
2
Live zero error
(X)
(X)
6-01
4
Mains phase loss
X
5
DC link voltage high
X
6
DC link voltage low
X
7
DC overvoltage
X
X
8
DC undervoltage
X
X
13
Overcurrent
X
X
X
14
Ground fault
X
X
X
15
Hardware mismatch
X
X
16
Short-circuit
X
X
17
Control word timeout
(X)
(X)
8-04
23
Internal fan fault
X
24
External fan fault
X
14-53
29
Heatsink temp
X
X
X
Diagnostics and Troubleshoo...
VLT
®
AQUA Drive FC 202 Low Harmonic Drive
74
Danfoss A/S © 10/2015 All rights reserved.
MG21B322
7
7