[23]
Maintenance Text 3
[24]
Maintenance Text 4
[25]
Maintenance Text 5
NB!
The Preventive Maintenance Events are defined in a 20 element array. Hence each Preventive Maintenance Event must use the same
array element index in par.23-10
to par.23-14
.
23-11 Maintenance Action
Option:
Function:
Select the action to be associated with the Preventive Maintenance Event.
[1] *
Lubricate
[2]
Clean
[3]
Replace
[4]
Inspect/Check
[5]
Overhaul
[6]
Renew
[7]
Check
[20]
Maintenance Text 0
[21]
Maintenance Text 1
[22]
Maintenance Text 2
[23]
Maintenance Text 3
[24]
Maintenance Text 4
[25]
Maintenance Text 5
23-12 Maintenance Time Base
Option:
Function:
Select the time base to be associated with the Preventive Maintenance Event.
[0] *
Disabled
Disabled
[0] must be used when disabling the Preventive Maintenance Event.
[1]
Running Hours
Running Hours
[1] is the number of hours the motor has been running. Running hours are not reset
at power-on. The
Maintenance Time Interval
must be specified in par.23-13
.
[2]
Operating Hours
Operating Hours
[2] is the number of hours the frequency converter has been running. Operating
hours are not reset at power-on. The
Maintenance Time Interval
must be specified in par.
[3]
Date & Time
Date & Time
[3] uses the internal clock. The date and time of the next maintenance occurrence
must be specified in par.23-14
23-13 Maintenance Time Interval
Range:
Function:
1 h*
[1 - 2147483647 h]
Set the interval associated with the current Preventive Maintenance Event. This parameter is only
used if
Running Hours
[1] or
Operating Hours
[2] is selected in par.23-12
The timer is reset from par.23-15
Example:
A Preventive Maintenance Event is set up Monday at 8:00. par.23-12
is
Operating hours
[2] and par.23-13
is 7 x 24 hours=168 hours. Next
Maintenance Event will be indicated the following Monday at 8:00. If this Maintenance Event is not
reset until Tuesday at 9:00, the next occurrence will be the following Tuesday at 9:00.
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
203