NB!
Set par. 1-03
Torque Characteristics
before tuning takes place.
22-30 No-Flow Power
Range:
Function:
0.00 kW*
[0.00 - 0.00 kW]
Read out of calculated No Flow power at actual speed. If power drops to the display value the
frequency converter will consider the condition as a No Flow situation.
22-31 Power Correction Factor
Range:
Function:
100 %*
[1 - 400 %]
Make corrections to the calculated power at par.22-30
.
If No Flow is detected, when it should not be detected, the setting should be decreased. However,
if No Flow is not detected, when it should be detected, the setting should be increased to above
100%.
22-32 Low Speed [RPM]
Range:
Function:
0 RPM*
[0 - par. 22-36 RPM]
To be used if par.0-02
has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 50% level.
This function is used for storing values needed to tune No Flow Detection.
22-33 Low Speed [Hz]
Range:
Function:
0 Hz*
[0.0 - par. 22-37 Hz]
To be used if par.0-02
has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 50% level.
The function is used for storing values needed to tune No Flow Detection.
22-34 Low Speed Power [kW]
Range:
Function:
0 kW*
[0.00 - 0.00 kW]
To be used if par.0-03
has been set for International (parameter not visible if
North America selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-35 Low Speed Power [HP]
Range:
Function:
0 hp*
[0.00 - 0.00 hp]
To be used if par.0-03
has been set for North America (parameter not visible if
International selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-36 High Speed [RPM]
Range:
Function:
0 RPM*
[0 - par. 4-13 RPM]
To be used if par.0-02
has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
187
2