2.15.5 16-5* Ref. & Feedb.
Parameters for reporting the reference and feedback input.
16-50 External Reference
Range:
Function:
0.0 N/A*
[-200.0 - 200.0 N/A]
View the total reference, the sum of digital, analog, preset, bus and freeze references, plus catch-
up and slow-down.
16-52 Feedback [Unit]
Range:
Function:
0.000 Proc-
essCtrlU-
nit*
[-999999.999 - 999999.999 Proc-
essCtrlUnit]
View value of resulting feedback value after processing of Feedback 1-3 (see par.16-54
and par. 16-56) in the feedback manager.
See par. 20-0*
Feedback
.
The value is limited by settings in par. 20-13 and par. 20-14. Units as set in par. 20-12
Reference/
Feedback Unit
.
16-53 Digi Pot Reference
Range:
Function:
0.00 N/A* [-200.00 - 200.00 N/A]
View the contribution of the Digital Potentiometer to the actual reference.
16-54 Feedback 1 [Unit]
Range:
Function:
0.000 Proc-
essCtrlU-
nit*
[-999999.999 - 999999.999 Proc-
essCtrlUnit]
View value of Feedback 1, see par. 20-0*
Feedback
.
The value is limited by settings in par. 20-13
Minimum Reference/Feedb.
and par. 20-14
Maximum
Reference/Feedb.
. Units as set in par. 20-12
Reference/Feedback Unit
.
16-55 Feedback 2 [Unit]
Range:
Function:
0.000 Proc-
essCtrlU-
nit*
[-999999.999 - 999999.999 Proc-
essCtrlUnit]
View value of Feedback 2, see par. 20-0*
Feedback
.
The value is limited by settings in par. 20-13 and par. 20-14. Units as set in par. 20-12
Reference/
Feedback Unit
.
16-56 Feedback 3 [Unit]
Range:
Function:
0.000 Proc-
essCtrlU-
nit*
[-999999.999 - 999999.999 Proc-
essCtrlUnit]
View value of Feedback 3, see par. 20-0*
Feedback
.
The value is limited by settings in par. 20-13
Minimum Reference/Feedb.
and par. 20-14
Maximum
Reference/Feedb.
. Units as set in par. 20-12
Reference/Feedback Unit
.
16-59 Adjusted Setpoint
Option:
Function:
View value of the adjusted set point according to par.20-29.
2.15.6 16-6* Inputs and Outputs
Parameters for reporting the digital and analog IO ports.
16-60 Digital Input
Range:
Function:
0*
[0 - 63]
View the signal states from the active digital inputs. Input 18 corresponds for example to bit 5. '0'
= NO signal, '1' = connected signal.
VLT
®
AQUA Drive Programming Guide
2 Parameter Description
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
153
2