50/60 Hz earth (ground) loops
With very long control cables, earth loops (ground loops)
may occur. To eliminate earth (ground) loops, connect one
end of the screen-to-earth (ground) with a 100 nF
capacitor (keeping leads short).
100nF
FC
PE
PE
PLC
130BB609.11
Illustration 2.26
Avoid EMC noise on serial communication
This terminal is connected to earth (ground) via an internal
RC link. Use twisted-pair cables to reduce interference
between conductors. The recommended method is shown
below:
PE
FC
PE
FC
130BB923.11
PE
PE
69
68
61
69
68
61
1
2
Illustration 2.27
1
Min. 16 mm
2
2
Equalizing cable
Table 2.9
Alternatively, the connection to terminal 61 can be
omitted:
PE
FC
PE
FC
130BB924.11
PE
PE
69
69
68
68
1
2
Illustration 2.28
1
Min. 16 mm
2
2
Equalizing cable
Table 2.10
2.5.4 Control Terminal Types
Terminal functions and default settings are summarized in
2.5.6 Control Terminal Functions
.
1
4
2
3
130BA012.11
61
68
69
39
42
50
53
54
55
12
13
18
19
27
29
32
33
20
37
Illustration 2.29 Control Terminal Locations
•
Connector 1 provides four programmable digital
input terminals, two additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage
•
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
•
Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output
•
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software
•
Also provided are two Form C relay outputs that
are in various locations depending upon the
frequency converter configuration and size
•
Some options available for ordering with the unit
may provide additional terminals. See the manual
provided with the equipment option
Installation
VLT
®
AQUA Drive D-Frame
Operating Instructions
28
MG21A202 - VLT
®
is a registered Danfoss trademark
2
2
Содержание VLT AQUA Drive D-Frame
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions 110 400 kW D Frame VLT AQUA Drive FC 200...
Страница 3: ...Safety VLT AQUA Drive D Frame Operating Instructions MG21A202 VLT is a registered Danfoss trademark...
Страница 86: ...www danfoss com drives MG21A202 130R0289 MG21A202 Rev 2012 06 15...
Страница 87: ......