8-06 Reset Control Word Timeout
This parameter is active only when
Hold set-up
[0] has been
selected in
Option:
Function:
[0]
*
Do not reset Retains the set-up specified in
8-04 Control
Word Timeout Function
, following a control
word time-out.
[1]
Do reset
Returns the unit to the original set-up
following a control word time-out. The unit
performs the reset and then immediately
reverts to the
Do not reset
[0] setting
6.5.2 8-3* FC Port Settings
8-30 Protocol
Option:
Function:
[0]
*
FC
Communication according to the FC Protocol
as described in the
VLT AutomationDrive
Design Guide, RS485 Installation and Set-up
.
[1]
FC MC
Select the protocol for the FC (standard) port.
[2]
*
Modbus RTU
8-31 Address
Range:
Function:
Size related
*
[1. - 255. ] Enter the address for the FC (standard)
port.
Valid range: 1 - 126.
8-32 FC Port Baud Rate
Option:
Function:
[0]
2400 Baud
Baud rate selection for the FC (standard)
port.
[1]
4800 Baud
[2]
*
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
8-35 Minimum Response Delay
Range:
Function:
10 ms
*
[Application
dependant]
Specify the minimum delay time
between receiving a request and
transmitting a response. This is used
for overcoming modem turnaround
delays.
8-36 Max Response Delay
Range:
Function:
Application
dependent
*
[Application
dependant]
Specify the maximum
permissible delay time
8-36 Max Response Delay
Range:
Function:
between transmitting a
request and receiving a
response. Exceeding this delay
time will cause control word
time-out.
8-37 Max Inter-Char Delay
Range:
Function:
Application
dependent
*
[Application
dependant]
Specify the maximum
permissible time interval
between receipt of two bytes.
This parameter activates time-
out if transmission is
interrupted.
This parameter is active only
when
is set to
FC
MC
[1] protocol.
8-53 Start Select
Option:
Function:
Select control of the unit start function via the
terminals (digital input) and/or via the fieldbus.
[0]
Digital
input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial
communication port or fieldbus option.
[2]
Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
NOTE
This parameter is active only when
is set
to [0]
Digital and control word
.
8-55 Set-up Select
Option:
Function:
Select control of the unit set-up selection via
the terminals (digital input) and/or via the
fieldbus.
[0]
Digital
input
Activates the set-up selection via a digital
input.
[1]
Bus
Activates the set-up selection via the serial
communication port or fieldbus option.
[2]
Logic AND Activates the set-up selection via the fieldbus/
serial communication port, AND additionally
via one of the digital inputs.