VL
T®
7
000
Booster
EMC test results (Emission, Immunity)
The following test results have been obtained using a system with a frequency converter (with options if relevant), a screened control cable, a control box with potentiometer, as well as a motor and motor cable.
Emission
Environment
Industrial environment
Housing, trades and light industries
VLT 7002- 7011/ 380- 460V
Basic standard
EN 55011 Class A1
EN 55011 Class B
EN 61800- 3
Setup
Motor cable
Conducted 150 kHz-
30 MHz
Radiated 30 MHz- 1 GHz
Conducted 150 kHz-
30 MHz
Radiated 30 MHz- 1 GHz
Conducted/ radiated 150
kHz- 30 MHz
300 m unscreened/ unarmoured
Yes
1)
No
No
No
Yes/ No
50 m br. screened/ armoured
(Bookstyle 20m )
Yes
Yes
Yes
No
Yes/ Yes
VLT 7000 Booster with RFI filter option
150m br. screened/ armoured
Yes
Yes
No
No
Yes/ Yes
300 m unscreened/ unarmoured
Yes
No
No
No
Yes/ No
50 m br. screened/ armoured
Yes
Yes
Yes
No
Yes/ Yes
VLT 7000 Booster with RFI- filter
(+ LC- module)
150m br. screened/ armoured
Yes
Yes
No
No
Yes/ Yes
Emission
Environment
Industrial environment
Housing, trades and light industries
VLT 7016- 7072 / 380- 460 V
Basic standard
EN 55011 Class A1
EN 55011 Class B
Setup
Motor cable
Conducted 150 kHz-
30 MHz
Radiated 30 MHz- 1 GHz
Conducted 150 kHz-
30 MHz
Radiated 30 MHz- 1 GHz
300 unscreened/ unarmoured
No
No
No
No
VLT 7000 Booster w/ o RFI filter option
150 m br. screened/ armoured
No
Yes
No
No
300 m unscreened / unarmoured
Yes
1)
No
No
No
50 m br. screened/ armoured
Yes
Yes
Yes
No
VLT 7000 Booster with RFI- module
150 m br. screened/ armoured
Yes
Yes
No
No
1) Depending on installation conditions
In order to minimise the conducted noise to the mains supply and the radiated noise from the frequency converter system, the motor cables should be as short as possible and the
screen ends should be made in accordance with the section on electrical installation.
MG
.70.
A
1
.0
2
-
V
LT
is
a
re
gist
e
re
d
D
a
nfoss
tra
d
e
ma
rk
127
Содержание VLT 7000 Series
Страница 13: ...VLT 7000 Booster Introduction to Booster Ordering form MG 70 A1 02 VLT is a registered Danfoss trademark 13...
Страница 22: ...VLT 7000 Booster Mechanical dimensions MG 70 A1 02 VLT is a registered Danfoss trademark 22...
Страница 30: ...VLT 7000 Booster MG 70 A1 02 VLT is a registered Danfoss trademark 30...