VLT
®
6000 HVAC
All about VLT 6000
HVAC
Automatic Motor Adaptation running (AMA RUN)
Automatic motor adaptation has been enabled in
parameter 107
Automatic Motor Adaptation, AMA.
Automatic Motor Adaptation completed
(AMA STOP)
Automatic motor adaptation has been completed.
The frequency converter is now ready for operation
after the
Reset
signal has been enabled. Please
note that the motor will start after the frequency
converter has received the
Reset
signal.
Stand by (STANDBY)
The frequency converter is able to start the motor
when a start command is received.
Stop (STOP)
The motor has been stopped via a stop
signal from a digital input, [OFF/STOP] button
or serial communication.
DC stop (DC STOP)
The DC brake in parameter 114-116 has been enabled.
DRIVE ready (UN. READY)
The frequency converter is ready for operation, but
terminal 27 is a logic "0" and/or a
Coasting command
has been received via the serial communication.
Not ready (NOT READY)
The frequency converter is not ready for operation,
because of a trip or because OFF1, OFF2
or OFF3 is a logic ‘0
’
.
Start disabled (START IN.)
This status will only be displayed if, in parameter
599
Statemachine, Profidrive
[1] has been selected
and OFF2 or OFF3 is a logic ‘0
’
.
Exceptions XXXX (EXCEPTIONS XXXX)
The microprocessor of the control card has stopped
and the frequency converter is out of operation.
The cause may be noise on the mains, motor
or control cables, leading to a stop of the
control card microprocessor.
Check for EMC-correct connection of these cables.