MN.51.T1.02 - VLT is a registered Danfoss trademark
4
VLT
®
5000 DeviceNet and Allen Bradley Control logix 5550
■
Configuring the VLT 5000 with RS Networx
In this example we will only have one VLT 5000 set
up to address 4 and the Master (1756-DNB) set up
to address 0.
Start RS Networx and a new project.
First install the EDS file by using the EDS wizard
under TOOLS and IMPORT EDS FILE. The file can
be ordered from your local Danfoss sales company.
After you have powered up the system and
browsed for active nodes on the DeviceNet you
map the I/O area of the VLT 5000 DeviceNet card
to the 1756 DeviceNet Scanner.