VLT® 2800 Series

Installation

105

Motor current, I

M, N

has been programmed to

the rated motor current (see motor nameplate).

Parallel connection of motors

The adjustable frequency drive is able to control

several motors connected in parallel. The combined

total current consumption of the motors is not to

exceed the maximum rated output current (I

INV

) for

the adjustable frequency drive. If the motors are to

have different rpm values, use motors with different

rated rpm values. Motor frequency is changed

simultaneously, which means that the ratio between

the rated rpm values is maintained.

Problems may arise at start-up and when operating

at low rpm if the motor sizes are widely different.

This is because the small motors

relatively high

resistance in the stator calls for a higher voltage

at the start-up and at low rpm.

In systems with motors connected in

parallel, the electronic thermal relay (ETR)

of the adjustable frequency drive cannot

be used as motor protection for the individual motor.

Protection must be provided individually for each motor.

Motor cables

See Technical data for correct sizing of motor cable

cross-section and length. Always comply with national

and local regulations on cable cross-section.

NOTE

If an unshielded/unarmoured cable is used,

some EMC requirements are not complied with,

see

EMC test results

in the Design Guide.

If the EMC specifications regarding emission are

to be complied with, the motor cable must be

shielded/armoured, unless otherwise stated for the

RFI filter in question. It is important to keep the

motor cable as short as possible so as to reduce the

noise level and leakage currents to a minimum. The

motor cable shield must be connected to the metal

cabinet of the variable frequency drive and to the metal

cabinet of the motor. The shield connections are to

be made with the biggest possible surface area (cable

clamp). This is enabled by different installation devices

in different variable frequency drives. Mounting with

twisted shield ends (pigtails) is to be avoided, since

these spoil the shielding effect at high frequencies. If

it is necessary to break the shield to install a motor

isolator or motor relay, the shield must be continued

at the lowest possible HF impedance.

Brake connection

NOTE

Voltages up to 850 VDC occur on the terminals.

No. 81 82

Brake resistor

R-

R+ terminals

Connect the brake resistor wiring to drive terminals 81

and 82. The connection cable to the brake resistor

must be shielded/armored. Connect the shield to

both the ground of the drive and the brake resistor by

means of cable clamps. Dimension the cross-section

of the brake cable to match the brake torque.

Ground connection

Since the leakage currents to ground may be higher

than 3.5 mA, the adjustable frequency drive must

always be connected to ground in accordance with

applicable national and local regulations. To ensure

that the ground cable has good mechanical connection

to terminal 95, the cable cross section must be a

minimum 7 AWG (10 mm

2

). To improve protection

MG.28.A8.22 - VLT is a registered Danfoss trademark

17

Содержание VLT 28

Страница 1: ...onnected to the AC line Ensure that the AC line supply has been disconnected and that 4 minutes has passed before removing motor and AC line plugs 7 The DC bus terminals are another high voltage input...

Страница 2: ...nsions of VLT 2822 3 HP 200 240 Volts and VLT 2822 2840 3 5 HP 380 480 Volts All dimensions are in inches VLT 2822 200 240 Volt VLT 2822 2840 380 480 Volt The drawing below gives the mechanical dimens...

Страница 3: ...N3110 RFI 1B filter 195N3103 Terminal cover The drawing below gives the dimensions for NEMA 1 terminal covers for VLT 2803 2875 Dimension a depends on the unit type IP 21 solution MG 28 A8 22 VLT is a...

Страница 4: ...2815 380 480 V 195N2118 47 80 170 VLT 2822 200 240 V VLT 2822 2840 380 480 V 195N2119 47 95 170 VLT 2840 200 240 V VLT 2855 2875 380 480 V 195N2120 47 145 170 VLT 2880 2882 380 480 V 195N2126 47 205 2...

Страница 5: ...VLT 2800 Series 192H4720 192H4893 MG 28 A8 22 VLT is a registered Danfoss trademark 8...

Страница 6: ...l be reduced without applicable derating The requirements that apply to enclosures and remote mounting must be complied with to avoid serious injury or equipment damage especially when installing larg...

Страница 7: ...as a high leakage current and must be grounded properly for safety Follow all local safety regulations High frequency grounding Keep grounding cables as short as possible Connect all grounds to ensure...

Страница 8: ...requencies Use cable clamps instead It is important to ensure good electrical contact from the installation plate through the installation screws to the metal cabinet of the variable frequency drive U...

Страница 9: ...pigtails as these increase shield impedance at higher frequencies 3 Protection with respect to ground potential between PLC and VLT f the ground potential between the VLT variable frequency drive and...

Страница 10: ...800 Series Installation Diagram Integrated 1A RFI filter and brake is an option VLT 2803 2815 200 240 V is not supplied with intermediate circuit coils MG 28 A8 22 VLT is a registered Danfoss trademar...

Страница 11: ...VLT 2800 Series Electrical installation VLT 2803 2815 200 240 V 2805 2815 380 480 V VLT 2822 200 240 V 2822 2840 380 480 V MG 28 A8 22 VLT is a registered Danfoss trademark 14...

Страница 12: ...n VLT 2840 200 240 V 2855 2875 380 480 V VLT 2880 2882 380 480V Please note that the units will be supplied with two bottom plates one for metric glands and one for conduits MG 28 A8 22 VLT is a regis...

Страница 13: ...x 220 240 V L2 L1 L3 No 95 Ground connection No 91 92 93 AC line voltage 3 x 380 480 V L1 L2 L3 No 95 Ground connection 380 460 Volt units with RFI filters may not be connected to AC line supplies in...

Страница 14: ...cable must be shielded armoured unless otherwise stated for the RFI filter in question It is important to keep the motor cable as short as possible so as to reduce the noise level and leakage current...

Страница 15: ...ng lowering applications you need to be able to control an electromagnetic brake The brake is controlled using a relay output or digital output terminal 46 The output must be kept closed voltage free...

Страница 16: ...with a clamp Normally the shield must also be connected to the chassis of the controlling device See the instructions for the specific device In analog signals or connections using very long wires 50...

Страница 17: ...ls 67 68 and 69 Normally this terminal is not to be used 1 The terminals are not valid for DeviceNet See the DeviceNet manual MG 90 BX YY for further details NOTE To supply internal 24 VDC voltage to...

Страница 18: ...ub D PIN 3 GND PIN 8 P RS 485 PIN 9 N RS 485 Sub D plug An LCP 2 control unit can be connected to the Sub D plug on the control card Ordering number 175N0131 LCP control units with ordering number 175...

Страница 19: ...Par 303 Digital input Stop inverted 6 Par 304 Digital input Coasting stop inverted 2 Par 305 Digital input Jog 13 Speed up slow down Speed up slow down using terminals 29 33 Par 302 Digital input Sta...

Страница 20: ...VLT 2800 Series Installation Par 316 Terminal 60 max scaling 20 mA MG 28 A8 22 VLT is a registered Danfoss trademark 23...

Страница 21: ...selecting parameters and for changing parameter values These keys are also used in Display mode for selecting the display of an operating value The QUICK MENU keys must be pressed at the same time to...

Страница 22: ...The display shows that in parameter 128 Motor thermal protection the selection made is Thermistor trip 2 Quick menu Using the QUICK MENU key it is possible to access the 12 most important parameters o...

Страница 23: ...otor For best possible tuning it is recommended that AMT be performed on a cold motor Repeated AMT runs can cause motor heating resulting in an increase in the stator resistance As a rule however this...

Страница 24: ...y drive receives an external reference through the control terminals as analog or digital signals In Auto mode use the and keys to scroll through the display of drive status messages In Hand mode it i...

Страница 25: ...ings alarms Warnings or alarms appear in the LED display as a numerical code Err xx A warning is displayed until the fault has been corrected while an alarm will flash until the STOP RESET key is pres...

Страница 26: ...section If a cable with a larger cross section is required it is recommended to reduce the output current by 5 for each step that the cable cross section is increased Increased cable cross section lea...

Страница 27: ...d in this manual have been adhered to Apply power to the unit Enter motor nameplate data into drive through Quick Menu 1 Parameter 102 MOTOR POWER in kW See conversion table in parameter 102 Motor Pow...

Страница 28: ...and JOG keys on the condition that these are active 3 the FWD REV key on the condition that is has been selected as active in parameter 016 Local reversing and that parameter 013 Local control is set...

Отзывы: