5
VMBQE102
3
Adjustment
3 .1 Ventilation
The ventilation flow must be adjusted according to the Building regulation norms.
If there is a chart, the airflow is adjusted according to the airflow specified on the chart.
Kitchen flues from kitchen fans or hoods must not be connected to the system.
The fan capacity is described in the diagram on page 4 and is set according to the instructions on page 6.
3 .2 Piping installation
The water flow through the Danfoss Vent heat recovery unit must be 0.15 l/s (9.0 l/min) if the air flow is
between 40 l/s-80 l/s.
When installing DHP-A and Danfoss Vent, the water flow must be 0.02 l/s if the airflow is between 40 l/s –
80 l/s.
Pressure drop chart, Water coil