Pressure switches
Pressure sensor
Discharge thermostat
Temperature sensor
Protection
Control
Example 1 with limited speed range from 30rps (1800rpm) to 120rps (7200rpm)
Safeties required
High pressure switch, Low pressure switch, Discharge gas thermostat set @135°C (275°F) if
necessary see Discharge temperature protection.
Drive setting
Adjust the minimum and maximum reference (speed setpoint) limits accordingly:
Par. 3-02 Minimum reference 1800 rpm (30 rps).
Par. 3-03 Maximum reference 7200 rpm (120 rps).
Envelope control
The unit controller continuously measures evaporating and condensing temperatures in order to
maintain the compressor within the envelope independently of compressor speed.
© Danfoss | Climate Solutions | 2023.08
AB392939083370en-000202 | 35
Scroll compressors, VCH115 | Application