A Maximum 150 mA
C Maximum 250 mA
B +24 V out
Illustration 47: Maximum Loads on +24 V/EXT+24 V Output
7.3.2.1 Digital Input Signal Inversions
The active signal level is different when the common inputs CMA and CMB (terminals 11 and 17) are connected to +24 V or to ground
(0 V).
The 24 V control voltage and the ground for the digital inputs and the common inputs (CMA, CMB) can be internal or external.
A
B
e
3
0
b
g
0
1
5
.1
0
DIN1
+24V
GND
DIN2
DIN3
CMA
+24V
GND
DIN1
DIN2
DIN3
CMA
A Positive logic (+24 V is the active signal) = the input is active
when the switch is closed.
B Negative logic (0 V is the active signal) = the input is active
when the switch is closed. Set the jumper X3 to the position
'CMA/CMB isolated from ground'.
Illustration 48: Positive/Negative Logic