12.3 Cable and Fuse Sizes
12.3.1 List of Cable and Fuse Size Information
This topic lists the links to find the cable and fuse size tables for VACON™ NXS and NXP Air Cooled AC Drive.
•
12.3.2 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9
•
12.3.4 Cable and Fuse Sizes for 525–690 V, FR6 to FR9
•
12.3.6 Cable and Fuse Sizes for 380–500 V, FR10 to FR11
•
12.3.8 Cable and Fuse Sizes for 525–690 V, FR10 to FR11
For AC Drives in North America, see:
•
12.3.3 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9, North America
•
12.3.5 Cable and Fuse Sizes for 525–690 V (UL Rating 600 V), FR6 to FR9, North America
•
12.3.7 Cable and Fuse Sizes for 380–500 V, FR10 to FR11, North America
•
12.3.9 Cable and Fuse Sizes for 525–690 V (UL Rating 600 V), FR10 to FR11, North America
12.3.2 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9
Table 34: Cable and Fuse Sizes for VACON
®
NXS/NXP
Enclosure
size
Drive type
I
L
[A]
Fuse
(gG/gL) [A]
Mains, motor and
brake resistor cable Cu
(1)
[mm
2
]
Mains terminal [mm
2
]
Grounding terminal
[mm
2
]
FR4
0003 2—0008 2
0003 5—0009 5
3–8
3–9
10
3*1.5+1.5
1–4
1–4
0011 2—0012 2
0012 5
11–12
12
16
3*2.5+2.5
1–4
1–4
FR5
0017 2
0016 5
17
16
20
3*4+4
1–10
1–10
0025 2
0022 5
25
22
25
3*6+6
1–10
1–10
0031 2
0031 5
31
31
35
3*10+10
1–10
1–10
FR6
0048 2
0038 5—0045 5
48
38–45
50
3*10+10
2.5–50 Cu
6–50 Al
2.5–35
0061 2
0061 5
61
63
3*16+16
2.5–50 Cu
6–50 Al
2.5–35
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G
| 137
Danfoss A/S ©
2018.06