Index
Parameter
Min
Max
Unit Default
ID
Description
P2.8.6
Number of tries after overcurrent trip
0
3
-
0
722 -
P2.8.7
Number of tries after 4 mA reference trip
0
10
-
0
723 -
P2.8.8
Number of tries after motor temperature fault trip
0
10
-
0
726 -
P2.8.9
Number of tries after external fault trip
0
10
-
0
725 -
P2.8.10
Number of tries after underload fault trip
0
10
-
0
738 -
6.4.10 Keypad Control (Control Panel: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed below. See the
Keypad control
menu in the
User Manual of the product.
Table 44: Keypad Control Parameters, M3
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.1
Control place
1
3
-
1
125
1 = I/0 terminal
2 = Keypad
3 = Fieldbus
P3.2
Keypad reference
P2.1.1
P2.1.2
Hz
0.00
-
-
P3.3
Direction (on keypad)
0
1
-
0
123
0 = Forward
1 = Reverse
P3.4
PID reference
0.00
100.00
%
0.00
167
-
P3.5
PID reference 2
0.00
100.00
%
0.00
168
-
R3.4
Stop button
0
1
-
1
114
0 = Limited function of Stop button
1 = Stop button always enabled
6.4.11 System Menu (Control Panel: Menu M6)
For more information related to the general use of the AC drive, such as selecting application and language, customized parameter
sets, or hardware and software, see the User Manual of the product.
6.4.12 Expander Boards (Control Panel: Menu M7)
The
M7
menu shows the expander and option boards attached to the control board and board-related information. For more infor-
mation, see the User Manual of the product.
AB296635287482en-000301 / DPD00903
76 | Danfoss A/S © 2023.02
PID Control Application
VACON® NX All-in-One
Application Guide