Table 120: Overvoltage Reference Level
ID 1262
Brake chopper in use
Brake chopper not in use
0 = High Voltage
500 V Unit: 844 V
690 V Unit: 1164 V
500 V Unit: 797 V
690 V Unit: 1099 V
1 = Normal Voltage
1.25*Estimated DC nominal voltage
1.18*Estimated DC nominal voltage
2 = Brake Chopper Level
1.07*brake chopper level
Brake chopper level
10.473 (ID 1267) Brake Chopper Level
Location in the menu:
P2.4.24
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the brake chopper level.
This parameter defines brake chopper control activation level in voltage. This parameter is active when ID 1262 Overvoltage refer-
ence selection is 2 = Brake Chopper Level.
For 400 V supply: 400*1.35*1.18 = 638 V DC
For 500 V supply: 500*1.35*1.18 = 797 V DC
For 690 V supply: 690*1.35*1.18 = 1100 V DC
10.474 (ID 1276) Quick Stop Mode
Location in the menu:
P2.4.18
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select how the drive stops when the quick stop command is given from DI or Fieldbus. Defines the action
after the IO emergency input goes low.
10.475 (ID 1278) Torque Speed Limit, Closed Loop
Location in the menu:
P2.10.11
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select the output frequency limit mode for the torque control.
For the selection of this parameter in VACON
®
NXS drives, see
ID 644
.
10.476 (ID 1285) Positive Frequency Limit
Location in the menu:
P2.6.11
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the final frequency reference limit for the positive direction.
Maximum frequency limit for the drive.
10.477 (ID 1286) Negative Frequency Limit
Location in the menu:
P2.6.10
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the final frequency reference limit for the negative direction.
Minimum frequency limit for the drive.
10.478 (ID 1287) Motor Torque Limit
Location in the menu:
P2.6.13
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the maximum torque limit of the motoring side.
10.479 (ID 1288) Generator Torque Limit
Location in the menu:
P2.6.12
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the maximum torque limit of the generating side.
10.480 (ID 1289) Motor Power Limit
Location in the menu:
P2.6.15.20
(Multi-purpose Control Application)
Use this parameter to set the maximum power limit of the motoring side.
For Closed Loop control mode only.
AB296635287482en-000301 / DPD00903 | 285
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide