During Identification Run, the brake control is disabled (see
10.620 External Brake Control with Additional Limits (IDs 315, 316, 346–
Rising edge required to start after identification.
10.303 (ID 633) Start-up Torque, Forward
Location in the menu:
P2.6.14.12
(Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID Control Applica-
tion)
P2.6.17.12
(Multi-purpose Control Application, VACON
®
NXS)
P2.6.15.12
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the start-up torque for forward direction when StartUp Torque is in use.
Sets the start-up torque for forward direction when selected with parameter
ID 621
.
10.304 (ID 634) Start-up Torque, Reverse
Location in the menu:
P2.6.14.8
(Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID Control Applica-
tion)
P2.6.17.8
(Multi-purpose Control Application, VACON
®
NXS)
P2.6.15.8
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the start-up torque for reverse direction when StartUp Torque is in use.
Sets the start-up torque for reverse direction when selected with parameter
ID 621
.
10.305 (ID 636) Open Loop Torque Control Minimum Frequency
Location in the menu:
P2.10.8
(Multi-purpose Control Application)
Use this parameter to set the output frequency limit below which the drive operates in the frequency control mode.
Because of the nominal slip of the motor, the internal torque calculation is inaccurate at low speeds where is it recommended to use
the frequency control mode.
10.306 (ID 637) Speed Controller P-Gain, Open Loop
Location in the menu:
P2.6.13
(Multi-purpose Control Application, VACON
®
NXS)
P2.6.14.8
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the P gain for the speed controller.
10.307 (ID 638) Speed Controller I-Gain, Open Loop
Location in the menu:
P2.6.14
(Multi-purpose Control Application, VACON
®
NXS)
P2.6.14.9
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the I gain for the speed controller.
10.308 (ID 639) Open Loop Torque Control P Gain
Location in the menu:
P2.10.9
(Multi-purpose Control Application)
Use this parameter to set the P gain for the torque controller in the open loop control mode.
10.309 (ID 640) Open Loop Torque Control I Gain
Location in the menu:
P2.10.10
(Multi-purpose Control Application)
Use this parameter to set the I gain for the torque controller in the open loop control mode.
10.310 (ID 641) Torque Reference Selection
Location in the menu:
P2.10.4
(Multi-purpose Control Application)
Use this parameter to select the torque reference.
AB296635287482en-000301 / DPD00903 | 247
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide