Index
Parameter
Min
Max
Unit
Default
ID
Description
Ctrl sgn 2 = Enable pulse
P2.2.2
DIN 3 function
0
8
-
1
301
0 = Not used
1 = Ext. fault, closing cont.
2 = Ext. fault, opening cont.
3 = Run enable
4 = Acc./Dec. time select.
5 = Force cp. to I/O
6 = Force cp. to keypad
7 = Force cp. to fieldbus
8 = Reverse
P2.2.3
(1)
Analog input 2 reference offset
0
1
-
1
302
0 = 0–20 mA (0–10 V)
1 = 4–20 mA (2–10 V)
P2.2.4
Reference scaling minimum value
0.00
320.00
Hz
0.00
303
-
P2.2.5
Reference scaling maximum value
0.00
320.00
Hz
0.00
304
-
P2.2.6
Reference inversion
0
1
-
0
305
0 = Not inverted
1 = Inverted
P2.2.7
Reference filter time
0.00
10.00
s
0.10
306
0 = No filtering
P2.2.8
(2)
AI1 signal selection
-
-
-
A1
377
-
P2.2.9
(2)
AI2 signal selection
-
-
-
A2
388
-
1
Remember to place jumpers of block X2 according to the selection (0 or 1). See the User Manual of the product.
2
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
.
3.4.4 Output Signals (Control Panel: Menu M2 ->G2.3)
Table 8: Output Signals, G2.3
Index
Parameter
Min Max
Unit Default ID
Description
P2.3.1
(1)
Analog output 1 signal selection
0
-
-
A.1
464 -
P2.3.2
Analog output function
0
8
-
1
307 0 = Not used (20 mA/10 V)
1 = Output freq. (0–f
max
)
2 = Freq. reference (0–f
max
)
3 = Motor speed (0–Motor nominal speed)
4 = Motor current (0-I
nMotor
)
5 = Motor torque (0-T
nMotor
)
6 = Motor power (0-P
nMotor
)
7 = Motor voltage (0-U
nMotor
)
8 = DC-link volt (0–1000 V)
P2.3.3
Analog output filter time
0.00 10.00
s
1.00
308 0 = No filtering
P2.3.4
Analog output inversion
0
1
-
0
309 0 = Not inverted
AB296635287482en-000301 / DPD00903 | 21
Danfoss A/S © 2023.02
Standard Application
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......