Selec-
tion
number
Selection name
Description
Notes
spective control place are used (reference according to
parameters ID 343, ID 121, and ID 122).
The value of ID 125 (Keypad Control Place) does not
change.
When DIN 2 opens, the control place is selected ac-
cording to keypad control place selection.
6
Closing contact
Force control place to keypad
7
Closing contact
Force control place to fieldbus
8
Reverse
Contact open: Forward
If several inputs are programmed to reverse, one active
contact is enough to set the direction to reverse.
Contact closed: Reverse
9
Jogging speed
Contact closed: Jogging speed selec-
ted for frequency reference
See
10.22 (ID 124) Jogging Speed Reference
10
Fault reset
Contact closed: Resets all faults
-
11
Acceleration/ De-
celeration prohibi-
ted
Contact closed: No acceleration or
deceleration possible until the con-
tact is opened
-
12
DC-braking com-
mand
Contact closed: In Stop mode, the DC
braking operates until the contact is
opened. See
-
13
Motor potentiome-
ter UP
Contact closed: Reference increases
until the contact is opened.
-
A
B
t
t
ID515
DIN2
f
out
f
out
RUN
STOP
DIN2
RUN
STOP
e
3
0
b
h
0
3
5
.1
0
Illustration 42: DC Braking Command (Selection 12) Selected for DIN 2
A
Stop mode = Ramp
B
Stop mode = Coasting
10.78 (ID 320) AI1 Signal Range
Location in the menu:
P2.2.4
(Local/Remote Control Application, Multi-Step Speed Control Application)
P2.2.16
(PID Control Application
P2.2.2.3
(Multi-Purpose Control Application, Pump and Fan Control Application)
Use this parameter to select the range for the analog input signal.
For selection 'Customized', see parameters
ID 321
and
ID 322
.
AB296635287482en-000301 / DPD00903
194 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide