Table 24: Dimensions in mm (in inch) of the Opening and Drive Outline with Flange, FI8
Drive type
W1
W2
H1
H2
H3
H4
H5
Ø
0140 5
0062 6-0100 6
301
(11.85)
330
(12.99)
810
(31.89)
832
(32.76)
265
(10.43)
258
(10.16)
33
(1.30)
9
(0.35)
12.3 Cable and Fuse Sizes
For cable and fuse size information, see the following topics:
•
12.3.1 Fuse Sizes for 465–800 V DC (380–500 V AC)
•
12.3.2 Fuse Sizes for 640–1100 V DC (525–690 V AC)
•
12.3.3 Cable Sizes for 465–800 V DC (380–500 V AC)
•
12.3.4 Cable Sizes for 640–1100 V DC (525–690 V AC)
12.3.1 Fuse Sizes for 465–800 V DC (380–500 V AC)
Table 25: Fuse Sizes for 465–800 V DC (380–500 V AC)
Enclosure size
Drive type
I
L
[A]
Bussman aR fuse type
Fuse size
Fuse U
n
[V]
Fuse I
n
[A]
No. of fuses
FI4
NXI_0004 5
4.3
170M1560
000
690
20
2
NXI_0009 5
9
170M1562
000
690
63
2
NXI_0012 5
12
170M1562
000
690
63
2
FI6
NXI_0016 5
16
170M1565
000
690
63
2
NXI_0022 5
22
170M1565
000
690
63
2
NXI_0031 5
31
170M1565
000
690
63
2
NXI_0038 5
38
170M1567
000
690
100
2
NXI_0045 5
45
170M1567
000
690
100
2
FI7
NXI_0061 5
61
170M1568
000
690
125
2
NXI_0072 5
72
170M1570
000
690
200
2
NXI_0087 5
87
170M1570
000
690
200
2
NXI_0105 5
105
170M1571
000
690
250
2
FI8
NXI_0140
140
170M3819
1
690
400
2
Specifications
Operating Guide | VACON® NX Inverters FI4-FI8
AQ299433367205en-000101 / DPD00908
114 | Danfoss A/S © 2019.07
Содержание VACON NX FI6
Страница 1: ...Operating Guide VACON NX Inverters FI4 FI8...
Страница 2: ......
Страница 164: ...Operating Guide VACON NX Inverters FI4 FI8 AQ299433367205en 000101 DPD00908 164 Danfoss A S 2019 07...
Страница 165: ...Operating Guide VACON NX Inverters FI4 FI8 AQ299433367205en 000101 DPD00908 165 Danfoss A S 2019 07...