>2000 m (on request)
Chemical environment condi-
tions
IEC 60721-3-3: Class 3C2
Environment corrosion cate-
gory
According to ISO/EN 12944-2: C1 as default; C4 as an engineered op-
tion
Electromagnetic compatibili-
ty environment
IEC 61000-2-5: Industrial
Seismic zone/Ground acceler-
ation
Zone 2 (standard)
Zone 4 (optional, +SZ04)
System burn-in at factory be-
fore delivery
4 h minimum, according to IEEE 1566
ATEX area: Flammable prod-
uct/Zone
IEC 60079-10-1/2: as an engineered option, certified per EN
50495:2010
Noise level
≤85 dB(A) at 1 m from the enclosure
Structure
Dimension and weight
11.2 Power Ratings and Dimensions
Cabinet sheet metal thickness Doors and panels: 1.5 mm
Base: 5 mm
Cable entry
Input, motor, and control cables: Bottom and top
Cooling system
Type
Forced air cooling including fan monitoring.
Fan redundancy available as option, +QDFR.
External auxiliary AC voltage
for cooling fans (optional,
+QDEX)
380–460 V AC, 50 Hz
380–460 V AC, 60 Hz
Protection level
IEC
IP31 (standard)
IP42 (optional, +IP42)
UL
NEMA 1
Auxiliaries
Cabinet lights
In the control cabinet
Power cell bypass
Automatic via IGBT, 1 ms bypass time (optional, +PPCB)
UPS for control voltage (DC)
30 min running time
11.2 Power Ratings and Dimensions
11.2.1 IEC Ratings
AQ363633621020en-000201 / 172F3117 | 111
Danfoss A/S © 2021.06
Specifications
VACON® 1000
Operating Guide
Содержание VACON 1000
Страница 1: ...Operating Guide VACON 1000 drives danfoss com...