MCB closed: The input HV breaker is closed.
Startup ready: HV power of the drive is on and internal diagnosis is done.
There is a delay of 22 s after the HV power is turned on. The DSP transmits the "operation request" signal after transmitting
the main control ready state.
VFD running: The VACON® 1000 is running and the main control system has no active faults.
7.2.2 Dashboard
The dashboard shows real-time values of the drive status:
Grid voltage
Input current
Output voltage
Output current
Reference speed
Input power
Transformer temperature values
Output speed
7.2.3 Single-line Diagram
The single-line diagram shows the status of each switch connected to the drive, such as breakers and contactors.
7.3 Control Panel
The control side panel includes the main controls for the drive. These controls can be used in HMI operation mode:
To unlock the other function buttons in the control panel, press the
REQUEST
button. Otherwise the other function buttons are
disabled.
To start the drive, press the
START
button (in HMI operation mode). When the drive is running, this button is disabled. If the
drive is at ramp stop state or stop state, this button is enabled, and can be used to restart the drive.
To stop the drive, press the
STOP
button. Select either ramp stop or coast stop.
Make the speed setting by numerical setting or slider.
To reset the fault status of the drive, press the
RESET
button. When the drive is running, this button is disabled.
A
B
C
D
E
e3
0b
i7
34
.1
0
Illustration 56: Control Panel
AQ363633621020en-000201 / 172F3117
64 | Danfoss A/S © 2021.06
Human-Machine Interface
VACON® 1000
Operating Guide