6.2 EMC-compliant Installation
For cable selections in different EMC levels, see
To comply with the EMC levels, use a grommet when installing the motor cable at the two ends. For the EMC level C2, it is necessary to
have a 360º grounding of the shield with grommets in the motor end.
Table 14: Recommendations for Cables
Cable
type
Category C2
(1)
Category C3
(2)
Category C4
(2)
Motor ca-
ble
A symmetrical power cable with a compact low-impe-
dance shield.
A cable for the specified mains voltage.
We recommend an MCCMK, or an EMCMK cable. See
.
We recommend that the cable transfer impedance
(1–30 MHz) is a maximum of 100 mΩ/m.
A symmetrical power cable with a concentric protection wire.
A cable for the specified mains voltage.
We recommend an MCMK cable. See
.
Mains ca-
ble
A power cable for a fixed installation.
A cable for the specified mains voltage.
A shielded cable is not necessary.
We recommend an MCMK cable.
Control
cable
A shielded cable with a compact low-impedance shield, for example a JAMAK, or an SAB/ÖZCuY-O cable.
1
1
st
environment
2
2
nd
environment
For the definitions of EMC protection levels, see IEC/EN 61800-3 + A1.
A
C
B
e
3
0
b
g
0
7
9
.1
0
A
The PE conductor and the shield
C
The shield
B
The PE conductors
Illustration 9: Cables with PE Conductors
Electrical Installation
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711