5 Specifications
5.1 Power-dependent Specifications
DTC 302
N165
N232
N262
Typical shaft output at 400 V [kW]
165
232
262
Typical shaft output at 460 V [hp]
221
311
352
Enclosure IP21
D1h
D2h
D2h
Output current
Continuous (at 400 V) [A]
318
424
480
Continuous (at 460 V) [A]
263
350
443
Continuous kVA (at 400 V) [kVA]
179
252
285
Continuous kVA (at 460 V) [kVA]
179
252
285
Max. input current
Continuous (at 400 V) [A]
271
380
430
Continuous (at 460 V) [A]
235
330
374
Max. cable size: mains, motor, mm (AWG)
2x95 (2x3/0 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Max. external mains fuses [A]
400
550
630
Estimated power loss at 400 V [W]
4271
5232
6203
Estimated power loss at 460 V [W]
3561
4390
5830
Efficiency
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip [
°
F] ([
°
C])
230 (110)
Control card ambient trip [
°
F] ([
°
C])
158 (70)
149 (65)
149 (65)
Table 5.1 Mains Supply 3x380-500 V AC
DTC 302
N165
N232
Typical shaft output at 575 V [kW]
165
232
Typical shaft output at 575 V [hp]
221
311
Enclosure IP21
D1h
D2h
Output current
Continuous (at 575 V) [A]
205
286
Continuous kVA (at 575 V) [kVA]
179
252
Max. input current
Continuous (at 575 V) [A]
188
264
Max. cable size: mains, motor, mm (AWG)
2x95 (2x3/0)
2x185 (2x350)
Max. external mains fuses [A]
315
550
Estimated power loss at 575 V [W]
3873
5288
Weight, enclosure IP21 kg (lbs.)
62 (135)
125 (275)
Efficiency
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip [
°
F] ([
°
C])
230 (110)
Control card ambient trip [
°
F] ([
°
C])
167 (75)
176 (80)
Table 5.2 Mains Supply 3x575 V AC
•
The typical power loss is at nominal load conditions and expected to be within
±
15% (tolerance relates to variety
in voltage and cable conditions).
•
The losses are based on the default switching frequency. The losses increase significantly at higher switching
frequencies.
Specifications
Installation Guide
MG35Q202
Danfoss A/S © 01/2015 All rights reserved.
19
5
5