Danfoss TURBOCOR 100150-2 Скачать руководство пользователя страница 2

           

INSTRUCTIONS 

KIT NUMBER

:

 100150-2

 

DESCRIPTION

KIT –COOLING VALVES 

ASSEMBLY TT300 – R134a 

DOCUMENT No

:

700469-2

 

REV: 

A

.

2

 

 

 

 

 

CAUTION: 

Prior to starting the removal procedures, switch off the AC mains at the disconnect switch 
and then wait at least 10 minutes for capacitors to de-energize before removing covers. 
Install a lock-out device or place a placard at the switch, alerting others that compressor 
servicing is in progress. 

 

REMOVAL PROCEDURE: 

1. 

Release the six captive screws that secure the service-side cover. Lift away the 
cover.

 

2. 

Remove two nuts, which secure coils, on the solenoid plunger assembly.

 

3. 

Withdraw the coils and keep them in a safe place.

 

4. 

Using a

 

six point deep socket (15/16”), open the two valves- orifice and plunger 

assembly. 

5. 

Ensure threads are clean and free from residual sealant. 

6. 

Place smaller O-rings (901362)

 

and the

 

bigger O-rings (901363)

 

onto both

 

valve 

orifices (700802-3).

 

7. 

Lubricate the smaller O-rings (901362)

 

and the bigger O-rings (901363)

 

with a drop of 

‘O’- lube (900578) on both valve orifices (700802-3).

 

 

 

8. 

Fasten the

 

two

 

valve orifices (700802-3) into the holes and tighten them until 16 

N.m using deep socket (15/16”). 

9. 

Lubricate the solenoid tube (901963) O-ring with a drop of ‘O’- lube (900578). 