5.4. Cable Requirements
Cable
Condition
Specification
AC
5 wire cable
Copper
Outer diameter
18-25 mm
Insulation strip
All 5 wires
16 mm
Max. recommended cable length
TripleLynx CN
8 kW and 10 kW
2.5 mm
2
21 m
4 mm
2
34 m
6 mm
2
52 m
10 mm
2
87 m
Max. recommended cable length
TripleLynx CN
12.5 kW
4 mm
2
28 m
6 mm
2
41 m
10 mm
2
69 m
Max. recommended cable length
TripleLynx CN
15 kW
6 mm
2
34 m
10 mm
2
59 m
PE Cable diameter
at least
as phase cables
DC
Max. 1000 V, 12 A
Cable length
4 mm
2
- 4.8
Ω
/km
< 200 m*
Cable length
6 mm
2
- 3.4
Ω
/km
>200-300 m*
Mating connector
Multi-contact
PV-ADSP4./PV-ADBP4.
* The distance between inverter and PV array and back, plus the summarised length of the cables used for
PV array installation.
Table 5.4: Cable Requirements
Note:
Avoid power loss in cables of more than 1 % of nominal inverter rating.
Illustration 5.1: TripleLynx CN 8 kW Cable Losses [%] versus Cable Length [m]
5. Technical Data
L00410580-01_02
25
5