TP7001
8
GB
Option 30 - Set Temperature Upper Limit
This allows the upper limit of the thermostat setting
range to be limited. Press
+
until Option 30 is
displayed, use
V
or
Λ
to select required setting.
Can be set to any value between 40.0°C and 5°C in
0.5°C steps
Factory setting = 30°C
4.2 Entering Installer Advanced Programming
To access the Installer Advanced Programming Mode
follow the steps below:
a) Press and hold
V
and
PROG
for 3 seconds to enter
User Advanced Programming, the display will
change to look like the image opposite.
b) Press and hold
V
,
Λ
and
PROG
for 5 seconds to enter
Installer Advanced Programming, the display will
change to look like the image opposite.
c) Use
the
+
and
-
keys to scroll backwards and forwards
between options then the
V
and
Λ
keys to change
the option settings. The fl ashing digits in the centre
of the display indicate the number of the selected
option. The large characters in the top or bottom of
the display indicate the option value selected.
d) To return to
RUN
, press and hold
PROG
until the display returns
to previous
RUN
mode.