Fig.10

Fig.11

Selection of time 

or actual room 

temperature in main 

LCD display

Temporary 

override of 

programmed 

temperature

press
together

Frost 

Protection

Fig.9

Fig.12

Temporary User Overrides

The TP5000 has several useful overrides which can be selected without affecting the 
thermostat programming.
• 

Selection of time or actual room temperature in main LCD display

 – press 

and – together

 to change between settings  

(Fig. 9)

.

• 

Temporary override of programmed temperature

 – press  

Λ or V

 

until required 

temperature is displayed (override will automatically cancel at beginning of next 
programmed event)  

(Fig. 10)

.

• 

Frost Protection

 – a constant low temperature can be selected whilst away from 

home - press 

Λ and V

 

together (Fig.11)

. Then use 

Λ or V

 to select the required 

temperature. To return to automatic programming press 

Λ and V

 together again.

Battery Replacement

•  A low 

battery symbol will flash

 in the LCD display  

(Fig. 12)

 

You have 15 days to replace the battery before the unit will switch off. 

 •

Remove  old  batteries  and  insert  new  ones.  All  settings  including  time  are 

 •

maintained.
Press and release the 

 •

RESET

 button to restart the unit. 

(Fig. 1)

NB. If the display ever goes blank during normal operation, the batteries will need 
to be renewed with high quality alkaline cells. The reset button should be pressed 
to restart the unit. All times, dates and events will be retained and need not be re-
programmed.

If the property is owned by a landlord he may, for gas safety reasons, have instructed the installer 
to set the service interval timer.
If set a visual and audible warning will alert you that the boiler will need servicing within the next 
28 days. This warning is repeated each day at noon. (Fig. 15)
If the boiler is not serviced within 28 days the daily audible warning will sound continuously and 
can only be cancelled each day by pressing any button on the unit.
In addition, all overrides and programming buttons will be disabled and the heating and hot water 
will only operate for 15 minutes in each programmed hour.
As this is a gas safety feature only an installer can reset the service interval timer. This will be done 
as part of the boiler service as part of the boiler service.

Service Interval Timer

Fig. 15

 

 

Commissioning Instructions

If the thermostat and the receiver have been supplied together in a combined pack, the 
units have been paired in the factory and no commissioning is required (RX1 only).

To tune the RX receiver to the frequency of the thermostat signal, follow steps 1-5 below.

 

Step 1 
TP5000-RF Si - 

Reset the unit by pressing the recessed reset button.

Step 2

 

Press and hold 

V and +

 buttons 

(fig. 13)

 for 3 seconds (TP5000 RF Si now transmits unique signal 

continuously for 3 minutes).

Step 3 
RX1 - 

Press and hold buttons 

PROG and CH1

 for 3 seconds until green light flashes once. 

(Fig. 14)
Step 4 (Fig.14)
RX2 (if applicable)

Stat 1 - perform steps 1-3 and 5. 
Stat 2 -perform steps 1-2 and then press 

PROG and CH2 on RX2.

RX3  (if applicable)

 

Stat 1 - perform steps 1-3 and 5.
Stat 2 - perform steps 1-2 and then press 

PROG and CH2 on RX3 then step 5.

Stat 3 - perform steps 1-2 and then press 

PROG and CH3 on RX3.

Step 5 
TP5000Si-RF - 

Press 

V or

  

Λ

  to select temperature - the unit will revert back to operating mode. 

I M P O R T A N T   R F   M o d e l s   o n l y

To  ensure  that  the  factory  programmes  are  set  and  the  micro-computer  is  operating  correctly 
it  is  essential  that  you  press  and  hold  the  RESET  button  before  you  begin  any  commissioning  or 
programming. 

Fig.13

Fig.14