Installation Guide
Termix VVX-I
6.1.4 AVTB controller (30–100 °)
The temperature setting is as follows:
1 = 35 °C
2 = 55 °C
3 = 75 °C
4 = 95 °C
5 = 100 °C
The values are intended as a guide.
Thermostatic control
The temperature of the HE flow line is adjusted as follows:
To increase temperature, turn the handle on the thermostatic
controller to select a higher number.
To decrease temperature, turn the handle on the thermostatic
controller to select a lower number.
6.1.5 Flow controller with integrated control valve
The controller is a self-acting flow controller with integrated control
valve. The controller closes when set max. flow is exceeded and
can be used in combination with Danfoss electrical actuators with
or with out safety function. Spring return motor can be used as
safety function by power failure.
6.1.6 Electronic control
Substations with electronic control must be set in accordance with
manufacturer´s instructions.
Where the room temperature is controlled by radiator thermostats,
it is recommended that thermostats be set for minimum
temperature in each room.
Danfoss District Energy