Danfoss Termix VMTD-F-B Скачать руководство пользователя страница 10

Termix VMTD-F-B - substation for direct HE and DHW

Instructions

DEN-GT

VI.CW.C1.02 / LUK40110  

©  Danfoss 04/2011

10

Troubleshooting  HE

Problem

Possible cause

Solution

Too little or no heat.

Strainer clogged in DH or HE circuit 

(radiator circuit).

Clean gate/strainer.

The filter in the heat meter on DH circuit 

clogged.

Clean the filter (after consulting the DH 

plant operator).

Defective or wrongly adjusted 

differential pressure controller.

Check the operation of the differential 

pressure controller – clean the valve 

seat if required.

Sensor defective – or possibly dirt in the 

valve housing.

Check the operation of the thermostat - 

clean the valve seat if required. 

Automatic controls, if any, wrongly set 

or defective - possibly power failure.

Check if the setting of the controller 

is correct – see separate instructions. 

Check the power supply. Temporary 

setting of motor to “manual” control – 

see instructions on automatic controls.

Pump out of operation.

Check if the pump is receiving power 

and that it turns. Check if there is air 

trapped in the pump housing - see 

pump manual.

The pump is set at too low speed of 

rotation.

Set the pump at higher speed of 

rotation.

Pressure drop – the pressure drop on 

the radiator circuit shows lower than 

recommended operating pressure.

Fill water on the system and check the 

functioning of the pressure expansion 

vessel if required.

Air pockets in the system.

Vent the installation thoroughly.

Limiting of the return temperature 

adjusted too low.

Adjust according to instructions.

Defective radiator valves.

Check – replace.

Uneven heat distribution in building 

because of incorrectly set balancing 

valves, or because there are no 

balancing valves.

Adjust/install balancing valves.

Diameter of pipe to substation too small 

or branch pipe too long.

Check pipe dimensions.

Uneven heat distribution.

Air pockets in the system.

Vent the installation thoroughly.

DH supply temperature 

too high.

Wrong setting of thermostat or of 

automatic controls, if any.

Adjust automatic controls, - see 

instructions for automatic controls.

Defective controller. The controller does 

not react as it should according to the 

instructions.

Call automatic controls manufacturer or 

replace the regulator.

Defective sensor on self-acting 

thermostat.

Replace thermostat, - or sensor only.

DH supply temperature 

too low.

Wrong setting of automatic controls, 

if any.

Adjust automatic controls – see 

instructions for automatic controls.

Defective controller. The controller does 

not react as it should according to the 

instructions.

Call in automatic controls manufacturer 

or replace controller.

Defective sensor on self-acting 

thermostat.

Replace thermostat - or sensor only. 

Wrong placement/fitting of outdoor 

temperature sensor.

Adjust location of outdoor temperature 

sensor. 

Strainer clogged.

Clean gate/strainer.

Содержание Termix VMTD-F-B

Страница 1: ...rect heating and instantaneous domestic hot water Table of Contents Declaration of conformity 2 Safety notes 3 Storage 3 Disposal 3 Mounting 4 Pipe connections 4 Electrical connection 5 Filling start...

Страница 2: ...60204 1 Safety of machinery Electrical equipment of machines EMC Directive 2004 108 EEC EN 61000 6 2 2007 Electromagnetic compatibility Generic standard Immunity industry EN 61000 6 3 2007 Electromag...

Страница 3: ...ed permissible operating parameters are exceeded The substation installation must be equipped with safety valves however always in accordance with local regulations Warning of hot surface The substati...

Страница 4: ...ith the station it must be fitted according to schematic diagram Please note that the strainer may be supplied loose Pipe connections Internal installation and district heating pipes connections must...

Страница 5: ...be disconnected for repairs Filling start up Prior to installation all substation pipes and connections should be cleaned and rinsed Before start up check that pipes are connected according to the cir...

Страница 6: ...tion might look different than the substation shown Schematic diagram example HE supply HE return DHW CWM DH supply DH return DCW Substations as supplied may be different to those shown on Danfoss lit...

Страница 7: ...DHW temperature control used in Danfoss substations DHW temperature should be adjusted to 45 50 C as this provides optimal utilisation of DH water At DHW temperatures above 55 C the possibility of lim...

Страница 8: ...U Pressure Equalizer The GTU Pressure Equalizer absorbs the expansion on the secondary side of the Termix water heaters and can be used as a substitute to the safety valve Furthermore the pressure equ...

Страница 9: ...n line clogged Clean strainer s DHW circulation pump out of order or with setting too low Check circulation pump Defective or clogged non return valve Replace clean No electricity Check Wrong setting...

Страница 10: ...the functioning of the pressure expansion vessel if required Air pockets in the system Vent the installation thoroughly Limiting of the return temperature adjusted too low Adjust according to instruc...

Страница 11: ...the radiators as low as ever possible while maintaining a reasonable level of comfort The system is single pipe loop The system should feature electronic controls as well as return sensors Pump pressu...

Страница 12: ...HE and DHW Instructions 12 VI CW C1 02 LUK40110 Produced by Danfoss A S 04 2011 Gemina Termix A S Member of the Danfoss Group Navervej 15 17 DK 7451 Sunds Denmark Tel 45 9714 1444 Fax 45 9714 1159 ma...