Termix VMTD-F-B
5.2 Schematic diagram
DHW
CWM
DCW
DH
Supply
HE
Supply
DH
Return
HE
Return
Your substation might look different than the schematic diagram shown.
Schematic description
B
Heat exchanger, DHW
31
Differential pressure controller
7
Thermostatic valve, DHW
41A Fitting piece, cold water mains
9
Strainer
41B Fitting piece, energy meter
14 Sensor pocket, energy meter
DHW:
Domestic Hot Water
CWM:
Cold Water Mains
DCW:
Domestic Cold Water
DH Supply:
District Heating Supply
DH Return:
District Heating Return
HE Supply:
Heating Supply
HE Return:
Heating Return
5.2.1 Technical parameters
Technical parameters
Nominal pressure:
PN 10 (PN 16 versions are available on enquiry)
Max. DH supply temperature:
120 °C
Min. DCW static pressure:
0.5 bar
Brazing material (HEX):
Copper
Heat exchangers test pressure:
30 bar
Sound level:
≤ 55 dB
Danfoss District Energy
VI.CW.C3.02 / LUK40110