Operating guide

Termix One Solar

7.0 Troubleshooting

7.1 Troubleshooting in general

In the event of operating disturbances, the following basic features
should be checked before carrying out actual troubleshooting:

the substation is connected to electricity,

the strainer on the DH supply pipe is clean,

the supply temperature of the DH is at the normal level
(summer, at least 60 °C - winter, at least 70 °C),

the differential pressure is equal to or higher than the normal
(local) differential pressure in the DH network – if in doubt, ask
the DH plant supervisor,

pressure on the system - check the HE pressure gauge.

Authorized personnel only

Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.

7.2 Troubleshooting DHW

Problem

Possible cause

Solution

Strainer in supply or return line clogged.

Clean strainer(s).

DHW circulation pump out of order or with
too low setting.

Check circulation pump.

Defective or clogged non-return valve.

Replace – clean.

No electricity.

Check.

Wrong setting of automatic controls, if any.

To adjust an electronic controller for
DHW, pls. note enclosed instructions for
electronic controller.

Scaling of the plate heat exchanger.

Replace – rinse out.

Defective motorized valve.

Check (use manual function) – replace.

Defective temperature sensors.

Check – replace.

Too little or no DHW.

Defective controller.

Check – replace.

DCW is being mixed with the DHW, e.g. in
a defective thermostatic mixing valve.

Check – replace.

Hot water in some taps but not in all.

Defective or clogged non-return valve on
circulation valve.

Replace – clean.

Tap temperature too high; DHW tap load
too high.

Thermostatic valve adjusted to a too high
level.

Check – set.

Scaling of the plate heat exchanger.

Replace – rinse out.

Temperature drop during tapping.

Larger DHW flow than the substation has
been designed for.

Reduce DHW flow.

Thermostatic control valve does not close

Temperature difference between DH
supply and DHW set point too low.

Lower the set point temperature or
increase the DH supply temperature.

12

DEN-GT

VI.CW.K4.02 / LUK38004

Danfoss District Energy

Содержание Termix One Solar

Страница 1: ...5 4 1 Mounting 5 4 2 Electrical connections 7 5 0 Design 8 5 1 Design 8 5 2 Schematic diagram 9 6 0 Controls 10 6 1 DHW temperature control 10 6 2 Maintenance 11 7 0 Troubleshooting 12 7 1 Troublesho...

Страница 2: ...Operating guide Termix One Solar 2 DEN GT VI CW K4 02 LUK38004 Danfoss District Energy...

Страница 3: ...mp together with a thermostat can maintain the circulating temperature at a desired temperature Domestic hot water DHW The domestic hot water is prepared in the heat exchanger and the temperature is r...

Страница 4: ...s circumstances interrupt all energy sources to the station if possible and seek expert help In case of discoloured or bad smelling domestic hot water close all shut off valves on the substation infor...

Страница 5: ...water DCW 2 Domestic hot water DHW 3 Buffer Tank BT supply 4 Buffer Tank BT return 5 Hot water circulation HWC Optional Connection sizes BT G int thread DCW DHW HWC G int thread Dimensions mm Without...

Страница 6: ...se Prior to installation all substation pipes and connections should be cleaned and rinsed Tightening Due to vibration during transport all substation connections must be checked and tightened before...

Страница 7: ...Disconnection The substation must be electrically connected so that it can be disconnected for repairs Outdoor temperature sensor Outdoor sensors should be mounted so as to avoid exposure to direct su...

Страница 8: ...look different than the substation shown Design description B Heat exchanger DHW 35 Ball valve non return valve M Electrical wiring box 45 Flow switch O Termix sensor accelerator 48 Air vent manual 7...

Страница 9: ...Termix sensor accelerator 11A DHW pump with built in check valve 45 Flow switch 1 Ball valve 13 Charging pump 48 Air vent manual 2 Single check valve 21 To be ordered separately 63 Sieve DHW Domestic...

Страница 10: ...t its best at DH supply temperatures of up to 90 C Thermostatic control DHW temperature is adjusted as follows To increase temperature turn the handle on the thermostatic controller to select a higher...

Страница 11: ...arameters such as meter readings Temperatures Checking of all temperatures such as DH supply temperature and DHW temperature Connections Checking all connections for leakages Safety valves The operati...

Страница 12: ...tive or clogged non return valve Replace clean No electricity Check Wrong setting of automatic controls if any To adjust an electronic controller for DHW pls note enclosed instructions for electronic...

Страница 13: ...Disposal Disposal This product should be dismantled and its components sorted if possible in various groups before recycling or disposal Always follow the local disposal regulations Danfoss District E...

Страница 14: ...Operating guide Termix One Solar 14 DEN GT VI CW K4 02 LUK38004 Danfoss District Energy...

Страница 15: ...Operating guide Termix One Solar 8 0 Declaration 8 1 Declaration of conformity Category 0 with electrical equipment Danfoss District Energy VI CW K4 02 LUK38004 DEN GT 15...

Страница 16: ...Operating guide Termix One Solar Produced by Danfoss A S 11 2016...

Отзывы: