Installation Guide

Termix One-B – 1 Series BS

7.0 Troubleshooting

7.1 Troubleshooting in general

In the event of operating disturbances, the following basic features
should be checked before carrying out actual troubleshooting:

the substation is connected to electricity,

the strainer on the DH supply pipe is clean,

the supply temperature of the DH is at the normal level
(summer, at least 60 °C - winter, at least 70 °C),

the differential pressure is equal to or higher than the normal
(local) differential pressure in the DH network – if in doubt, ask
the DH plant supervisor,

pressure on the system - check the HE pressure gauge.

Authorized personnel only

Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.

7.2 Troubleshooting DHW

Problem

Possible cause

Solution

Strainer in supply or return line clogged.

Clean strainer(s).

DHW circulation pump out of order or with
too low setting.

Check circulation pump.

Defective or clogged non-return valve.

Replace – clean.

No electricity.

Check.

Wrong setting of automatic controls, if any.

To adjust an electronic controller for
DHW, pls. note enclosed instructions for
electronic controller.

Scaling of the plate heat exchanger.

Replace – rinse out.

Defective motorized valve.

Check (use manual function) – replace.

Defective temperature sensors.

Check – replace.

Too little or no DHW.

Defective controller.

Check – replace.

DCW is being mixed with the DHW, e.g. in
a defective thermostatic mixing valve.

Check – replace.

Hot water in some taps but not in all.

Defective or clogged non-return valve on
circulation valve.

Replace – clean.

Tap temperature too high; DHW tap load
too high.

Thermostatic valve adjusted to a too high
level.

Check – set.

Scaling of the plate heat exchanger.

Replace – rinse out.

Temperature drop during tapping.

Larger DHW flow than the substation has
been designed for.

Reduce DHW flow.

Thermostatic control valve does not close

Temperature difference between DH
supply and DHW set point too low.

Lower the set point temperature or
increase the DH supply temperature.

LGB38000

DEN-GT

11

Содержание Termix One-B-1 BS Series

Страница 1: ...1 Safety Notes general 3 4 0 Mounting 4 4 1 Mounting 4 5 0 Design 6 5 1 Design 6 5 2 Schematic diagram 7 6 0 Controls 9 6 1 DHW temperature control 9 6 2 Maintenance 10 7 0 Troubleshooting 11 7 1 Tro...

Страница 2: ...water very efficiently thereby creating a very good operation economy Domestic hot water DHW The domestic hot water is prepared in the heat exchanger and the temperature is regulated with a thermostat...

Страница 3: ...leaks or other dangerous circumstances interrupt all energy sources to the station if possible and seek expert help In case of discoloured or bad smelling domestic hot water close all shut off valves...

Страница 4: ...supply Connections 1 Domestic cold water DCW 2 Domestic hot water DHW 3 District heating DH supply 4 District heating DH return Connection sizes DH G int thread DCW DHW G int thread Dimensions mm Typ...

Страница 5: ...tallation Clean and rinse Prior to installation all substation pipes and connections should be cleaned and rinsed Tightening Due to vibration during transport all substation connections must be checke...

Страница 6: ...mix One B 1 Series BS 5 0 Design 5 1 Design Your substation might look different than the substation shown Design description B Heat exchanger DHW O Termix sensor accelerator 7 Thermostatic controller...

Страница 7: ...ermix One B with GTU Second diagram Termix One B with safety valve Schematic description B Heat exchanger DHW 7 Thermostatic valve 2 Single check valve 21 To be ordered separately 4 Safety valve 62 GT...

Страница 8: ...BS 5 2 1 Technical parameters Technical parameters Nominal pressure PN 16 Max DH supply temperature 120 C Min DCW static pressure 0 5 bar Brazing material HEX Copper Heat exchangers test pressure 30...

Страница 9: ...supply temperatures of up to 90 C Thermostatic control DHW temperature is adjusted as follows To increase temperature turn the handle on the thermostatic controller to select a higher number To decrea...

Страница 10: ...e energy meter at regular intervals and to write down the meter readings Regular inspections of the substation according to this Instruction are recommended which should include Strainers Cleaning of...

Страница 11: ...k circulation pump Defective or clogged non return valve Replace clean No electricity Check Wrong setting of automatic controls if any To adjust an electronic controller for DHW pls note enclosed inst...

Страница 12: ...x One B 1 Series BS 7 3 Disposal Disposal This product should be dismantled and its components sorted if possible in various groups before recycling or disposal Always follow the local disposal regula...

Страница 13: ...Installation Guide Termix One B 1 Series BS LGB38000 DEN GT 13...

Страница 14: ...Installation Guide Termix One B 1 Series BS 14 DEN GT LGB38000...

Страница 15: ...cts Substations Category 0 without electrical equipment covered by this declaration are in conformity with the following directives standards and other normative documents provided that they are used...

Страница 16: ...Installation Guide Termix One B 1 Series BS Produced by Gemina Termix A S 02 2015...

Отзывы: