Operating Guide
Termix BTD RO MIX
6.2 DHW temperature control
DHW temperature control
There are various types of DHW temperature control used in
Danfoss substations.
DHW temperature should be adjusted to 45-50 °C, as this provides
optimal utilisation of DH water. At DHW temperatures above 55 °C,
the possibility of lime scale deposits increases significantly.
6.2.1 RAVK controller
RAVK controller (25-65 °C). The temperature setting is as follows:
1 = 25 °C
2 = 35 °C
3 = 45 °C
4 = 55 °C
5 = 65 °C
The values are intended as a guide.
Thermostatic control
DHW temperature is adjusted as follows:
To increase temperature, turn the handle on the thermostatic
controller to select a higher number.
To decrease temperature, turn the handle on the thermostatic
controller to select a lower number.
6.2.2 AVTB controller (20–60 °)
The temperature setting is as follows:
1 = 20 °C
2 = 35 °C
3 = 50 °C
4 = 60 °C
5 = 70 °C
The values are intended as a guide.
The AVTB operates at its best at DH supply temperatures of up to
90 °C.
Thermostatic control
DHW temperature is adjusted as follows:
To increase temperature, turn the handle on the thermostatic
controller to select a higher number.
To decrease temperature, turn the handle on the thermostatic
controller to select a lower number.
Danfoss District Energy
VI.HE.F2.02 / LUK40661
DEN-GT
13
Содержание Termix BTD RO MIX
Страница 20: ...Operating Guide Termix BTD RO MIX 20 DEN GT VI HE F2 02 LUK40661 Danfoss District Energy...
Страница 21: ...Operating Guide Termix BTD RO MIX Danfoss District Energy VI HE F2 02 LUK40661 DEN GT 21...
Страница 22: ...Operating Guide Termix BTD RO MIX 22 DEN GT VI HE F2 02 LUK40661 Danfoss District Energy...
Страница 24: ...Operating Guide Termix BTD RO MIX Produced by Danfoss A S 02 2017...