Commissioning
6.4 Commissioning via PDM
42
SONO 3500 CT
Operating Instructions, 07/2019, VI.SH.P2.02
6.4.3
Adding the device to the network
It is recommended to configure the project in PDM before setting the parameters.
1. Add device to SIMATIC Modbus network:
–
Select "File" → "New"
Type in a project name, e.g. SONO 3500 CT
–
Right click on "Net" and select "Insert New Object" → "Modbus Net".
Your PC is now added to the Modbus Net
– Right click on "Modbus Net" and select "Inser
t New Object" → "Modbus Device"
–
Click on "Assign" and assign the Modbus device to SITRANS FUS/E080 (Sensors →
Flow → Ultrasonic → SIEMENS AG → SONO 3500 CT) and click "OK".
Rename device according to application requirements (max. 32 characters).
Set up communication parameters for SIMATIC Modbus network
–
Select "Net" → "Modbus Net", right click on "Modbus net" and select "Object
Properties"
– Select "Connection" to activate IrDA
6.4.4
Configuring the device
In the following it is described how to configure the device by defining all sensor specific
parameters.
Note
Measurement accuracy
A correct flowmeter installation is required to ensure optimum measurement accuracy.
Read all parameters
Before any parameterization is done it is necessary to read all parameters from the device
into the offline table of SIMATIC PDM. The offline table merely contains default data.
1. Open PDM device driver.
2. Select "Upload to PC/PG .." Select "Execute even if the device TAG does not match the
project data TAG.", and click "OK" to read all parameters to the offline table.
After closing the dialog box, all loaded parameters should show "Loaded" in the status of
the PDM table. For a complete parameter list, see Parameter lists (Page 73).
3. Store factory set default values on your local PC ("File"
→ "Export") in order to be able to
retrieve default settings.
Содержание SONO 3500 CT
Страница 1: ...Ultrasonic Flowmeter Operating Instructions SONO 3500 CT 07 2019 Edition ...
Страница 2: ......
Страница 8: ...Table of contents 6 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 14: ...Introduction 1 5 Further Information 12 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 38: ...Electrical connection 5 5 Sealing of SONO 3500 CT 36 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 50: ...Commissioning 6 4 Commissioning via PDM 48 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 54: ...Functions 7 4 Hardware key 52 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 64: ...Service and maintenance 8 7 Battery disposal 62 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...