Differential pressure switches 
Technical data

 

Neutral zone, 

p Nz

RT 260AL: 0.3 bar – 0.9 bar

RT 262AL: 0.1 bar – 0.33 bar

RT 263AL: 0.05 bar – 0.23 bar

RT 266AL: 0.05 bar – 0.23 bar

Max. test pressure, p' = 1.1 × MWP

Permissible temperature range: 

-40 °C – 70 °C

Contact load

See contact cover or fig. 3.

If the contact load is given as, for example, 

10 (4) A, 400 V AC, it means that the 

connected load must be max. 10 A ohmic and 

4 A inductive at 400 V AC.

The permissible starting current on motor 

cut-in can be up to seven times the inductive 

load, but max. 28 A.

The switch meets the requirements of 

VDE* 0660.

*VDE = Verband Deutscher Elektrotechniker

Installation

A set of Pg13.5 cable gland is attached to the 

RT in a separate bag. To ensure IP66 (units 

with automatic reset) or IP54 (units with 

external reset) grade of RT enclosure it is 

necessary to assemble this gland as shown in 

the fig. 4. If this gland is not used with a cable, 

a metal blinding should be also assembled.

The differential pressure control must be 

mounted on a valve panel or, for example, 

direct on a compressor. Use the fixing holes 

(25). If the unit can be exposed to vibration, it 

should to be mounted on a resilient pad.

Electrical connection

See fig. 5.

START = make. STOP = break

DIFF = fixed contact differential

Cable diameter: 6 – 14 mm

Connect earth to the earth screw (38)

Setting

Set the required differential pressure with the 

setting disc (5) while at the same time reading 

the scale (9). Find the required neutral zone 

for RT 260AL, RT 262AL, RT 263AL, RT 266AL 

from the diagram. The setting value for the 

Type

Differential 

pressure 

range 

p  

 

[bar]

Operation 

range for 

LP bellows 

 

[bar]

Mechani-

cal 

differen-

tial 

[bar]

Max. 

working 

pressure 

MWP 

[bar]

RT 260A

0.5 – 4

-1 – 18

0.3

22

RT 260A

0.5 – 6

-1 – 36

0.5

42

RT 260A

1.5 – 11

-1 – 31

0.5

42

RT 262A

0.1 – 1.5

-1 – 9

0.1

11

RT 265A

1 – 6

-1 – 36

0.5

42

RT 260AL

0.5 – 4

-1 – 18

0.3

22

RT 262AL

0.1 – 1.5

-1 – 9

0.1

11

RT 263AL

0.1 – 1.0

-1 – 6

0.05

7

RT 266AL

0 – 0.9

-1 – 6

0.05

7

Differenspressostater 
Tekniske data

 

Neutralzone, 

p Nz

RT 260AL: 0.3 bar – 0.9 bar

RT 262AL: 0.1 bar – 0.33 bar

RT 263AL: 0.05 bar – 0.23 bar

RT 266AL: 0.05 bar – 0.23 bar

Maks. prøvetryk, p' = 1.1 × PB

Tilladelig temperatur: -40 °C – 70 °C

Kontaktbelastning

Se kontaktdæksel eller fig. 3. 

Er kontaktbelastningen eksempelvis angivet 

som 10 (4) A, 400 V AC betyder det, at der 

maks. må tilsluttes 10 A ohmsk og 4 A 

induktiv belastning ved 400 V AC Maksimal 

startstrøm ved indkobling af motor må være 

op til syv gange den induktive belastning – 

dog maks. 28 A.

Kontaktsystemet opfylder betingelserne i 

*VDE = Verband Deutscher Elektrotechniker

 

Montering

Et sæt Pg13,5 kabelforskruning er vedlagt

Type

Differens-

trykområde 

p  

 

[bar]

Driftsom-

råde for 

LP-bælg 

 

[bar]

Mekanisk 

differens 

 

 

[bar]

Til- 

ladeligt 

drifts- 

tryk PB 

[bar]

RT 260A

0.5 – 4

-1 – 18

0.3

22

RT 260A

0.5 – 6

-1 – 36

0.5

42

RT 260A

1.5 – 11

-1 – 31

0.5

42

RT 262A

0.1 – 1.5

-1 – 9

0.1

11

RT 265A

1 – 6

-1 – 36

0.5

42

RT 260AL

0.5 – 4

-1 – 18

0.3

22

RT 262AL

0.1 – 1.5

-1 – 9

0.1

11

RT 263AL

0.1 – 1.0

-1 – 6

0.05

7

RT 266AL

0 – 0.9

-1 – 6

0.05

7

ENGLISH

DANSK

neutral zone (40) can be read from the lowest 

scale on the diagram. 

Example 1

RT 262A with terminals 1 – 4 connected. Set 

differential pressure 

p = 0.5 bar.  

The RT 262A breaks at a differential pressure 

of 0.5 bar and makes at a differential pressure 

+ contact differential = 0.5 bar + 0.1 bar = 0.6 bar.

Example 2 

RT 262AL

Required differential pressure 

p = 0.5 bar. 

Required neutral zone Nz = 0.25 bar.

As can be seen on the diagram, fig. 6., the 

required neutral zone of 0.25 bar is obtained 

by setting the neutral zone disc (40) at 2.5.

Because the contact differential is 0.1 bar, the 

make and break differential pressures for the 

switch are: 

Make differential pressure for contacts 

1 – 4 = 0.5 bar + 0.1 bar = 0.6 bar.

Break differential pressure for contacts 

1 – 4 = 0.5 bar (= set value 

p).

Make differential pressure for contacts 

1 – 2 = 0.6 bar – 0.25 bar = 0.35 bar.

Break differential pressure for contacts 

1 – 2 = 0.35 bar + 0.1 bar = 0.45 bar.

produktet i en separat pose. For at sikre

kapslingsgrad IP66 (enheder med automatisk

reset) eller IP54 (enheder med ekstern

DANSK RESET) er det nødvendigt at montere

denne kabelforskruning som vist i fig. 4.

Hvis denne kabelforskruning ikke bruges

sammen med et kabel, bør der monteres

en blindprop (metal skive).

Differenspressostaten monteres på en ventilt-

avle eller f.eks. direkte på en kompressor. 

Benyt monteringshullerne (25).

Hvis apparatet kan blive udsat for vibrationer, 

bør det monteres på et blødt underlag.

El-tilslutning

Se fig. 5.

START = slutte. STOP = bryde DIFF = fast 

kontaktdifferens.

Kabeldiameter: 6 – 14 mm.

Jordforbindelse tilsluttes jordskruen (38).

Indstilling

Det ønskede differenstryk indstilles ved 

hjælp af indstillingsskiven (5) under samtidig 

aflæsning af skalaen (9).

Den ønskede neutralzone for RT 260AL, 

RT 262AL, RT 263AL, RT 266AL opsøges i 

diagrammet. På diagrammets nederste skala 

aflæses den værdi, neutralzonerullen (40) skal 

indstilles på.

Eksempel 1

RT 262A med klemme 1 – 4 tilsluttet.Indstillet 

differenstryk 

p = 0.5 bar.  

RT 262A bryder ved differenstrykket 

0.5 bar og slutter ved differenst 

kontaktdifferensen = 0.5 bar + 0.1 bar = 0.6 bar.

Eksempel 2

RT 262AL

Ønsket differenstryk 

p = 0.5 bar. 

Ønsket neutralzone Nz = 0.25 bar.

Som det kan ses af diagrammet fig. 5., opnås 

den ønskede neutralzone på 0.25 bar ved at 

indstille neutralzonerullen (40) på værdien 2.5.

Slutte- og brydedifferenstrykkene for 

kontaktsystemet (se fig. 4.) bliver herved, idet 

kontaktdifferensen er 0.1 bar: 

Sluttedifferenstryk for kontakterne 

1 – 4 = 0.5 bar + 0.1 bar = 0.6 bar.

Brydedifferenstryk for kontakterne 

1 – 4 = 0.5 bar (= indstillingsværdi, 

p). 

Sluttedifferenstryk for kontakterne 

1 – 2 = 0.6 bar – 0.25 bar = 0.35 bar.

Brydedifferenstryk for kontakterne 

1 – 2 = 0.35 bar + 0.1 bar = 0.45 bar.