GB - Installation Instructions
Commissioning
Prior to re-
fi
tting the thermostat to the wallplate, the DIL
switches on the rear of the unit must be set to the desired
setting.
DIL Switch options, shown in factory set position.
ON
On/Off
Chrono
Chrono 3
Chrono 6
°C
°F
No Comp Del
Comp Del
3 Minutes
4 Minutes
DB 2°C/4°F
DB 4°C/8°F
Fan Coil
Heat Pump
RV-
RV+
Sw On
1
2
3
4
5
6
7
8
DIL Switch descriptions
Switch 8
: If set to On/Off, both heating and cooling stages
operate in on/off mode. If set to Chrono, heating
stage operates in chrono-proportional modes,
cooling continues in On/off mode.