REPI Series Digital Thermostat Manual

Operations

 

On/Off:

 Press “ ” buttons to turn on; 

press “ ” again to turn off.

 

Setpoint:

 With thermostat on, press “ ” to 

reduce the setpoint, press “ ” to increase the 

setpoint, the setpoint step is

0.5 °C, the setpoint will be confirmed 

automatically after 5 seconds, and then return to 

dispay status, press “ ” or “ ” to check setpoint.

 

Mode

: With thermostat on, press “ ” to 

change the working mode – Cooling “ ”, 

Heating “ ”, Vent “ “, Auto “ ”

( Auto is available REPI-4/ REPI-4N).

 

Fan Speed:

 With thermostat on, press “ ” to 

select the desired speed – low speed “ ”, Med 

speed “ ”, High speed “ ”, auto “ ”. If single 

speed fan available, there’s only med speed “ ”.

Under auto speed fan, the fan speed will be 

changed automatically as below: in low speed 

when room temperature

is 1 °C difference with setpoint;in med speed 

when room temperature is 2 °C difference with 

setpoint; in High speed when

room temperature is 3 °C difference with 

setpoint.

 

Sleep

: Thermostat will get into sleep function 

after programming.The set Temperature should 

to be.

To set:

 Press “ ” button for 3 seconds till 

“ ” display, there’s a number of count down 

in the center of LCD, Use “ ” or “ ” to adjust 

the desired sleep time: the max. = 48 hours; 

thermostat will return to the working status after 

5 seconds, “ ” is flashing to start counting down. 

The setpoint should be replaced by the sleep 

setpoint.

To quit:

 When thermostat get into Sleep 

function, “ ” will flash, press “ ” or “ ” to quit.

 

Keypad lock:

 press “ ” and “ ” for 10 

seconds till to “ ” display to activate, under this 

function, any keypad is locked.

Press “ ” and “ ” for 10 seconds till “ ” 

disappear to quit the function.

 

Set Parameters:

 With thermostat off, press 

“ ” for 10 seconds to enter menu to set the 

parameters.

Parameter table

Parameter Description

Default

Range

Step

1

Power on status (0: Off; 1: On; 2: Hold)

2

0 - 2

2

Fan speed (0: Single Speed; 1: Three Speed)

1

0 - 1

3

Fan mode (DA; DB)

0

4

Sensor selection (0: Internal; 1: Remote)

1

0 - 1

5

Temperature format (0: Celsius; 1: Fahrenheit)

0

0 - 1

0.1

6

Temperature calibration

0

-20.0 - +20.0

0.1

7

Minimum setpoint

5 °C/41 °F

0 - 99.5

0.5

8

Maximum setpoint

35 °C/96

0 - 99.5

0.5

9

Dead band (REPI-4)

2

0 - 10

0.5

10

Heating & Auto sleep setpoint

7 °C/45 °F

0 - 99.5

0.5

11

Cooling sleep setpoint

28 °C/82

0 - 99.5

0.5

12

Comms# (REPI-2N;REPI-4N)

1

1 - 32

1

13

Input Signal Mode 0: Invalid

1: Changeover(REPI-2)

2: thermostat will be sleep without input signal 

3: thermostat will be Off without input signal

0

0 - 3

14

Heating reset time

90 sec.

10 - 300 sec.

10 sec.

15

Cooling reset time

90 sec.

10 - 300 sec.

10 sec.

16

Ports mode (0: Modulation & Floating; 1: On/Off)

0

0 - 1

17

Valve status as turn off (0: Close; 1:Hold; 2: Open )

0

0 - 2

18

Port1 Modulation direction (0:10V Open; 1:10V Close)

0

0 - 1

19

Port1 Modulation minimum signal

0Bit

0-128Bit(5V/10mA)

0.04V/Bit(0.08mA/Bit)

20

Port1 Modulation proportional

2

1 - 20

0.5

21

Port2 Modulation direction (0:10V Open; 1:10V Close)

0

0 - 1

22

Port2 Modulation minimum Signal

0 Bit

0-128Bit(5V/10mA)

0.04V/Bit(0.08mA/Bit)

23

Port2 Modulation proportional

2

1 - 20

0.5

24

Port1 Floating minimum time

1 sec.

1 - 9 sec.

1 sec.

25

Port1 Floating maximum time

30 sec.

10 - 300 sec.

10 sec.

26

Port1 Floating minimum time

1 sec.

1-9 sec.

1 sec.

27

Port1 Floating maximum time

30 sec.

10 - 300 sec.

10 sec.

28

Disable / Enable bypass PID control

(0: Disable; 1: Enable)

0

0-1

29

Override output value when bypass PID control

Display output value when enable PID control

0 - 255

Содержание REPI Series

Страница 1: ...mperature setting Fahrenheit or Celsius degree display Timing sleep Control On Off of cooling and heating equipment Selectable single speed or three speed fan control Order Guide Model Output signal Fan Single 3 speed RS485 Network Input Control Remote Sensor Floating Modulation REPI 2 Cooling Heating REPI 2N Cooling Heating REPI 4 Cooling Heating REPI 4N Cooling Heating Fan thermostat with fan fu...

Страница 2: ...isappear to quit the function Set Parameters With thermostat off press for 10 seconds to enter menu to set the parameters Parameter table Parameter Description Default Range Step 1 Power on status 0 Off 1 On 2 Hold 2 0 2 2 Fan speed 0 Single Speed 1 Three Speed 1 0 1 3 Fan mode DA DB 0 4 Sensor selection 0 Internal 1 Remote 1 0 1 5 Temperature format 0 Celsius 1 Fahrenheit 0 0 1 0 1 6 Temperature ...

Страница 3: ...ction 5 C 42 F 0 15 C 42 62 F 1 C 2 F 40 Stop temperature of Low temperature protection 7 C 46 F 2 17 C 46 66 F 1 C 2 F It will confirm itself 20 seconds later after setting and return to Off state Parameter table continuous Specification There is a 5 poles switch on PCB The meaning is below Location ON OFF 1 120 ohm Resistance between AB wires No Resistance between AB wires 2 Port 1 Modulation 0 ...

Страница 4: ...986404620en 010102 Data sheet REPI Series Digital Thermostat Manual Wiring diagram Note Be sure to connect all the wires as per the wiring diagrams and keep it away from water mud and other material so as to prevent the unit being spoiled ...

Отзывы: