Troubleshooting PM 

controller / Domestic hot water 

 
 

Problem 

 

Possible cause 

 

Solution 

In general: Does the PM 

controller work incorrectly 



 

If the quantity of tap water is normal (temperature unimportant) it 

indicates that the PM controller works correctly. 



 

Locate defect in another part 

of the installation (see below). 

In general: 

Are the operating 

conditions satisfactory?

 



 

The unit requires a primary flow temperature of minimum 60°C 

and a differential pressure during operation according to the 

information stated in the product sheet for the unit. 



 

Contact district heating 

supplier. 

PM controller leaking, 
Water leaking from Allen 

screws at central part of PM 

controller 



 

One of the two O-rings is defective (does not influence the PM 

control function). If a non-return valve is installed in the DCW inlet 

(e.g. in the house service connection or in DCW meter) a safety 

valve should be mounted between the non-return valve and the 

water heater. 



 

Replace PM controller (use 

new sealings). 

DHW tap load too low. 



 

 
The diaphragm of the PM controller is defective. 

 



 

 
Replace diaphragm or PM 
controller 
 

DHW tap load too low;  

Tap temperature too low;  

Tap temperature flunctuates; 



 

  PM controller wrongly adjusted. 

  Dirt strainer in primary flow clogged. 

  Defective non-return valve in thermostatic battery (DHW 

 

tap temperature lower than DHW from unit). 

  Defective non-return valve in hot-water circulation (circulation 

 

return pipe is getting cold during tapping of hot water). 

  Lime scale precipitation in plate heat exchanger for DHW  

 

(

t primary too low during DHW tapping). 

  Dirt in PM controller. 

  DCW flow too high (big nominal diameter of pipe, high DCW   

 

pressure); in total maximum 16-17 litre per minute         



 



 



 

 



 



 



 



 

 

See back of the page. 

Clean strainer. 

Clean or replace non-return 
valve. 

Clean or replace non-return 
valve. 

Replace plate heat exchanger 

Cleaning, see back of      
page 

DCW reduction can be 
added). 
 

Primary return water tempera-

ture too high while on stand-

by; Plate heat exchanger is 

cold.. 



 

 

Bypass thermostat is defective or wrongly adjusted. 

 



 

 

Replace or adjust by-pass 
thermostat correctly 

 

Primary return water tempera-

ture too high while on stand-

by; Plate heat exchanger is 

hot. 



 

Dirt (sand, iron splinter or similar) in PM controller. Controller 

does not close. Noise from flow can often be heard. 



 

Move handle several times 

between red and blue 

markings; at the same time 

make several hot-water 

tappings. 

Clean PM controller 

Primary return temperature 

too high during hot water 

tapping. 



 

Lime scale precipitation in the plate heat exchanger for DHW 



 

Replace plate heat exchanger 

Connecting pieces of the PM 

controller do not fit the unit 



 

In particular when replacing PM controller in old units. 



 

Loosen Allen screws; turn half 

of the PM controller 180°. 

 

 

 
 
Delivery address: 

 

 

 

 

 

Stamp / Telephone: 

 

 

 

 

 

 

Contact person: 

 

 

 

 

 

 

Customer’s address: 

 

 

 

 

Содержание Redan PM

Страница 1: ... druckgesteuert das heisst daß erst bei Warmwasserzapfung ein Durchfluss sowohl primär Fernwärme als auch sekundär Warmwasser durch den Wärmetauscher ermöglicht wird Es besteht ein Proportionalverhalten zwischen Fernwärmedurchfluss und der Warmwasserentnahme Dadurch gibt es keine Temperaturunterschiede bei kleinen oder grösseren Zapfmengen Einbau Der Regler muss so montiert werden daß derVolumenst...

Страница 2: ... temperature lower than DHW from unit Defective non return valve in hot water circulation circulation return pipe is getting cold during tapping of hot water Lime scale precipitation in plate heat exchanger for DHW t primary too low during DHW tapping Dirt in PM controller DCW flow too high big nominal diameter of pipe high DCW pressure in total maximum 16 17 litre per minute See back of the page ...

Страница 3: ...HW Cost free repairs Danfoss agrees to repair or replace at the discretion of Danfoss such Products that on Danfoss examination are found to be defective at the time of delivery due to faulty manufacture design and or defective materials provided Customer makes a claim to Danfoss within 12 months from the date of delivery however not exceeding 18 months from the date stamped on the product If defe...

Страница 4: ...defekt WW Zapftemperatur niedriger als WW Zuleitung Rückschlagventil in WW Zirkulation defekt Zirkulationsrohr wird kalt bei WW Zapfung Wärmeübertrager für WW verkalkt t primär zu niedrig während WW Zapfung Verschmutzung des PM Reglers Zu große KW Durchflußmenge große Rohrnennweiten hohe KW Druck insgesamt max 16 17 Liter pro Minute Siehe andere Seite Sieb reinigen Rückschlagventil reinigen oder a...

Страница 5: ...der Zapfstelle kontrollieren Empfohlene Zapftemperatur 45 48 C nie höher als 50 C um Kalkbildung im WW Bereiter zu vermeiden Sachmängelgewährleistung Danfoss verpflichtet sich innerhalb der gewährleistungsfristen die von ihr hergestellten und gelieferten Produkte nachzubessern oder auszutauschen wenn sie sich nach Überprüfung bei Danfoss als defekt erwiesen haben Alle Ansprüche des Käufers gleich ...

Страница 6: ...et Kontraventil på cirkulationsstreng defekt cirkulationsrør bliver koldt under varmtvandstapning Kontraventil på fjernvarme retur på vandvarmer defekt Vandvarmeren tilkalket dårlig afkøling under tapning Snavs i PM regulator Se bagside Rens snavssamler Rens eller skift kontraventil Rens eller skift kontraventil Rens eller skift kontraventil Afhjælpes ved udsyring Rens regulatoren Se bag side For ...

Страница 7: ...les ved at dreje håndtaget mod rød varmere eller blå koldere Temperaturen indstilles under varmtvandstapning 8 10 liter pr minut til 45 48 C Temperaturen bør aldrig overstige 50 C for at undgå kalk udfældning i vandvarmeren Vederlagsfri reparation Danfoss Redan A S forpligter sig til efter eget valg at repare re eller omlevere produkter som efter Danfoss Redan s undersøgelse viser sig at være mang...

Страница 8: ...Produced by Danfoss Redan A S 12 2010 Produced by Danfoss Redan A S 08 2013 ...

Отзывы: