VI.JA.C3.5B
1
2
Regler PCVD
p2
p1
p
0
50%
V
max
3
SW 22
4
7.6 Adjustment of the Setpoint
The setpoint of the pressure must be adjusted at
the pilot controller AVD
1
. The setpoint range is
indicated on the rating plate of the actuator.
Procedure
1. Prior to the differential pressure adjustment,
start the system as described in section 7.4.
The differential pressure can also be adjusted
while the bypass
2
is opened.
2. Adjust the flow rate at a valve in flowdirection
after the controller PCVD.
Value approx. 50 % of the max. flow rate
3
.
3. Adjustment of the pressure by turning the
setpoint adjuster
4
.
Turning to the right,
increases the setpoint
.
Turning to the left,
reduces the setpoint
.
7.7 Sealing
The setpoint adjusters may be sealed.
7.8 Function Test
Check the pressure of the running system with
different load situations.
If the pressure is exceeded in either direction,
adjust the pressure as described in section 7.6.