2. Product description
2.10 Refrigeration capacity
Model
OP-UPAC015COP04E
Outdoor air temperature
32 °C
Refrigerant
R744(CO2)
Evaporation
temperature (°C)
-45
7.09
-40
8.32
-35
10.2
-30
12.1
-25
13.9
-20
15.8
-15
17.7
-10
19.6
-5
20.9
0
20.0
5
19.8
Unit: kW
Notes:
1. This shows the case of refrigerant R744, power source voltage
400V, and gas cooler outdoor air temperature 32 °C.
2. The evaporating temperature is the saturated temperature of
the suction pressure, and shows the value when the suction gas
superheat degree is 10K.
3. When evaporating temperature exceeds -5°C, rated capacity
decreases due to the operation of the protection control, and
rated capacity decreases as the evaporation temperature
increases.
Notes:
1. When evaporating temperature exceeds -5°C, power consumption decreases due to the operation of the protection control,
and power consumption decreases as the evaporation temperature increases.
Refrigeration capacity list
Refrigeration capacity curve and power consumption curve
5.00
7.00
9.00
11.00
13.00
15.00
17.00
19.00
21.00
-50
-40
-30
-20
-10
10
0
Coolingcapacity (kW)
Evaporation temperature (ºC)
Power consumption (kW)
Evaporation temperature (ºC)
-50
-40
-30
-20
-10
0
10
6
8
10
12
Fig. 1
Fig. 2
17
AB408540130380en-000102
© Danfoss | Climate Solutions | 2023.02
Application Guidelines