1 – Introduction

These instructions pertain to Optyma G&D 
HBP DSH105 condensing units (R410A) 
used for refrigeration systems. They provide 
necessary information regarding safety and 
proper usage of this product.
The condensing unit includes following:
•  Scroll compressor
•  Microchannel heat exchanger
•  Fix low Pressure cartridge
•  Fix high pressures cartridge
•  Fix Fan control pressures cartridge
•  Service valves Suction/ liquid
•  Crankcase heater for compressor
•  Receiver with stop valve

2 – Handling and storage

•  It is recommended not to open the 

packaging before the unit is at the final 
place for installation.

•  Handle the unit with care. The packaging 

allows for the use of a forklift or pallet jack. 
Use appropriate and safe lifting equipment.

•  Store and transport the unit in an upright 

position.

•  Don’t expose the packaging to rain or 

corrosive atmosphere.

•  Store the unit between -35°C and 50°C.
•  After unpacking, check that the unit is 

complete and undamaged.

3 – Installation precautions

 Do not braze as long the condensing unit 

is under pressure.

 Never place the unit in a flammable 

atmosphere.

 IPlace the unit in such a way that it is not 

blocking or hindering walking areas, doors, 
windows or similar.
•  Ensure adequate space around the unit for 

air circulation and to open doors. Refer to 
picture1 for minimal values of distance to 
walls.

•  Avoid installing the unit in locations which 

are daily exposed to direct sunshine for 
longer periods.

•  Avoid installing the unit in aggressive and 

dusty environments.

•  Ensure a foundation with horizontal surface 

(less than 3° slope), strong and stable 
enough to carry the entire unit weight and 
to eliminate vibrations and interference.

•  The unit ambient temperature may not 

exceed 50°C during off cycle.

•  Ensure that the power supply corresponds 

to the unit characteristics (see nameplate).

•  When installing units for HFC refrigerants, 

use equipment specifically reserved for 
HFC refrigerants which was never used for 
CFC or HCFC refrigerants.

•  Use clean and dehydrated refrigeration-

grade copper tubes and silver alloy brazing 
material.

•  Use clean and dehydrated system 

components.

•  The suction piping connected to 

the compressor must be flexible in 
3 dimensions to dampen vibrations. 

Furthermore, piping has to be done in such 
a way that oil return for the compressor is 
ensured and the risk of liquid slug over in 
compressor is eliminated.

4 – Installation

•  The unit must be securely installed on a 

stable and rigid support and fixed from the 
beginning.

•  It is recommended to install the unit on 

rubber grommets or vibration dampers 
(not supplied).

•  Slowly release the nitrogen holding charge 

through the schrader port.

•  Connect the unit to the system as soon as 

possible to avoid oil contamination from 
ambient moisture.

•  Avoid material entering into the system 

while cutting tubes. Never drill holes where 
burrs cannot be removed.

•  Braze with great care using state-of-the-art 

technique and vent piping with nitrogen 
gas flow.

•  Connect the required safety and control 

devices. When the schrader port is used for 
this, remove the internal valve.

•  It is recommended to insulate the suction 

pipe up to the compressor inlet with 19mm 
thick insulation.

5 – Leak detection

 Never pressurize the circuit with oxygen 

or dry air. This could cause fire or explosion.
•  Do not use dye for leak detection.

Instructions

Optyma™ G & D HBP DSH105

OP-HRSM0750NC211Q / OP-HRSM0750NC211R

    OP-HRSM   0750             NCXXX     Q

1 2 3 4

5

6

7

1 Application

 

H = HBP/Universal

2 Design

 

R = Air cooled condenser, Twin fan, Scroll compressor

3 Refrigerant

 

S = R410A

4 Condenser

 

M = Microchannel condenser size 100°F Max Ambient

5 Unit SIze (Nominal HP)

 

HP rating in hundredths of HP, i.e.: 0033=1/3 HP, 1000 = 10HP

6 Version

 

NCXX = Customer specific unit with unique identification Number

7 Voltage code 

R = Compressor 460V/3ph/60Hz, Fan(s) 460V/1ph/60Hz
Q = Compressor 208-230V/3ph/60Hz, Fan(s) 230V/1ph/60Hz

 The condensing unit must only be used for its designed purpose(s) and 

within its scope of application.

 Under all circumstances, the EN378 (or other applicable local safety 

regulation) requirements must be fulfilled.

 The condensing unit is delivered under nitro- gen gas pressure (1 bar) 

and hence it cannot be connected as it is; refer to the «installation» section 
for further details.

 The condensing unit must be handled with cau- tion in the vertical 

position (maximum offset from the vertical: 15°)

Designation system

Warnings

Содержание Optyma OP-HRSM0750NC211Q

Страница 1: ... Use clean and dehydrated system components The suction piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations Furthermore piping has to be done in such a way that oil return for the compressor is ensured and the risk of liquid slug over in compressor is eliminated 4 Installation The unit must be securely installed on a stable and rigid support and fixed from the ...

Страница 2: ...alves must be in the open position Check compliance between unit and power supply Check that the crankcase heater is working Check that the fan can rotate freely Check that the protection sheet has been removed from the backside of condenser Balance the HP LP pressure Energize the unit It must start promptly If the compressor does not start check wiring conformity voltage on terminals and sequence...

Страница 3: ...transmit the model number and serial number with any claim filed regarding this product The product warranty may be void in following cases Absence of nameplate External modifications in particular drilling welding broken feet and shock marks Compressor opened or returned unsealed Rust water or leak detection dye inside the compressor Use of a refrigerant or lubricant not approved by Danfoss Any d...

Страница 4: ... Danfoss DCS CC 2020 05 Instructions 4 AN343545366322 000101 1554 800 696 1530 977 1554 800 1530 696 977 OP HRSM0750NC211R OP HRSM0750NC211Q ...

Страница 5: ...E B2 B3 BLUE BROWN BLUE BROWN BLACK BLACK BLACK BLACK BLACK BLACK S1 FC2 FC1 S2 Code Q OP HRSM0750NC211Q 230V 3Ph 60Hz WD1 WD2 Legend B1 Compressor B2 Fan Motor 1 B3 Fan Motor 2 FC1 Fan Cycling 1 FC2 Fan Cycling 2 L1 L2 L3 Power input R1 CrankCase Heater S1 S2 Terminal Block LP Low Pressure Switch HP High Pressure Switch Provided by Customer Code R OP HRSM0750NC211R 460V 3Ph 60Hz Legend B1 Compres...

Страница 6: ... This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved 6 AN343545366322 000101 Danfoss DCS CC 2020 05 ...

Отзывы: