7

FRCC.ES.010.A4.02

Manual

Controller Installation

Electrical installations

Commissioning

Main display (after controller 
start-up)

Parameter Menu

Quick start of the unit / 
Refrigerant change

•   Arrange electrical connections as mentioned in the table below
•  Remove temporarily bridge DI1 (terminals 24 - 25 of the controller) to get access to parameters and 

values of the controller without starting the condensing unit

•  The controller’s screen displays the Evaporation Temperature in °C
•  Press short the lower button of the controller to show the Condensing Temperature in °C
•  After a few seconds the display returns to the Evaporation Temperature in °C

•   To get access to parameter menu press 5 seconds the upper button of the controller 
•   The first Parameter “r05” of the Parameter menu will be shown on the display
•   Press short the upper (or lower) button to go to the next Parameter of the Parameter menu. Scroll fast 

through the Parameters with a long press on these buttons

•  Press short the middle button to show the value of the selected Parameter
•  Press afterwards the upper (or lower) button to change the value of the selected parameter. A long 

press on these buttons will change the value fast

•  The value will be stored after 20 seconds without any action or with a short press on the middle button
•   After 20 seconds without pressing any button, the display returns to the main screen, the evaporation 

temperature in °C. The parameter menu is closed now, to go back to the parameter menu press again 
upper button 5 seconds … 

•  Optyma Plus™ new generation is preset, depending on the compressor model and refrigerant type. 

In the case of a “multi-refrigerant” compressor, the controller of the condensing unit is set for R404A 
(see table on page3). If this factory setting fits for the requirement of your application, no controller 
parameter must be changed.

•   For a refrigerant change go into the parameter menu (press upper button 5 seconds)
•   Select parameter “r12” (software main switch) with a short press on lower button
•   Activate parameter “r12” with middle button and change the value to 0 (zero)
•   Confirm the value with a short press on the middle button (the 3 LED’s start flashing)
•   Go to the parameter “o30” (Refrigerant)
•   Change the value to 3 (stands for R134a), or 17 (R507), or 20 (R407C), or 19 (R404A)
•   Confirm the value with a short press on the middle button
•   Select parameter “r12” again
•   Change the value to 1 (one)
•   Confirm the value with a short press on the middle button (the 3 LED-signs stop flashing and the con-

densing unit will start if required)

•   After 20 seconds the display returns to the evaporation temperature in °C, the new refrigerant and all 

relevant parameters are changed

R404A *

Room Thermostat control without Pump Down 

function

R404A *

Pump Down control

with factory delivered low pressure transmitter 

- Connect Room Thermostat to these terminals

 

- Connect power supply to main switch acc. wir-

ing diagram, located in front door inner side

- Connect power supply to main switch acc. wir-

ing diagram, located in front door inner side

- Increase the Setting of controller Par. c33 (Pump 

Down CUT-OUT value):

e.g. Piston : 0,7bar

e.g. Scroll : 1,7bar

Note: To avoid low pressure alarm, the Setting of 

c33 should be higher than c75

*: change for other refrigerants following chapters.

Содержание OP-LPHM018SCP00G

Страница 1: ...Optyma PlusTM New Generation Controller Installation Manual http cc danfoss com...

Страница 2: ...2 FRCC ES 010 A4 ML Manual Controller Installation English version 7 French version 12 German version 18 Danish version 24 Contents...

Страница 3: ...x x x x x 33 OP MPUM068MLP00E 114X4311 MLZ030T4LC9 X x x x x x 34 OP MPUM080MLP00G 114X4321 MLZ038T5LC9 X x x x x x 35 OP MPUM080MLP00E 114X4324 MLZ038T4LC9 X x x x x x 36 OP MPUM108MLP00E 114X4344 M...

Страница 4: ...s til ledning nr 6 Optyma Plus Verfl ssigungss tze sind vorparametriert f r das installierte Verdichtermodell und verwendete K ltemittel Im Fall eines Verdichters f r mehrere K ltemittel z B MTZ oder...

Страница 5: ...Compressors limit switch Endschalter interrupteur 13 14 S1 2 X1 1 X1 N1 C1 BU BU BN N2 C2 PE BN N3 PE X1 BK BK 3 X1 BN BN BN P U 1 2 3 B2 22 X1 15 X1 20 X1 P B4 14 P B3 P 1 Option B5 2 BN BK GY I I I...

Страница 6: ...unction 8 Day Night Function 8 Service and Maintenance 8 Main Display 8 Operating Parameters 8 Alarm and Error Messages 9 Repair 9 Controller failure 9 Factory reset 9 Controller Replacement of a unit...

Страница 7: ...Plus new generation is preset depending on the compressor model and refrigerant type In the case of a multi refrigerant compressor the controller of the condensing unit is set for R404A see table on...

Страница 8: ...r 06 00 a m Select and set parameter t18 Night start hours e g 022 for 22 00 p m Select and set parameter t07 Clock setting hours e g 011 for 11 xx a m Select and set parameter t08 Clock setting minut...

Страница 9: ...terminal block from the controller or remove the complete controller Connect the condensing unit back to power supply turn hardware main switch on Controller failure if the controller fails there is a...

Страница 10: ...Reference 8 0K The Reference is accessible by pressing short the middle button of the controller When Reference is shown it can be modified with the upper or lower button Additionally to this the cont...

Страница 11: ...ction pres Param c75 Scroll 1 4bar Recip 0 4bar Low pressure switch Cut In Scroll 1 5bar Recip 0 5bar Suction Pressure Electronic Safety LP Mechanical Safety LP High pressure switch Cut In Scroll and...

Страница 12: ...tr leur Affichage permanent 14 Visualisation des param tres de fonctionnement 14 Alarmes et messages d erreur 15 D pannage 15 D faillance du contr leur 15 R initialisation du param trage usine 15 Remp...

Страница 13: ...es bornes Connectez l alimentation lectrique au sectionneur principal conform ment au sch ma lectrique situ sur la face interne de la porte avant Connectez l alimentation lectrique au sectionneur prin...

Страница 14: ...param tre c33 Scroll 1 7bar Piston 0 7bar c76 Scroll ou Piston 0 7bar Pression basse pressostat Cut Out Scroll 0 5bar Piston 0 3bar Pression basse transducteur Cut Out param tre c75 Scroll 1 4bar Pist...

Страница 15: ...aillance du contr leur En cas de d faillance du contr leur il est possible de faire fonctionner le groupe de condensation en mode manuel moyennant quelques adaptations mineures Pour ce faire effectuez...

Страница 16: ...sur le bouton du milieu du contr leur A ce stade en appuyant sur le bouton du haut ou du bas la valeur usine 8 0K est augment e bouton du haut ou diminu e bouton du bas chacune des impulsions exerc e...

Страница 17: ...asse transducteur param tre c75 Scroll 1 4bar Piston 0 4bar Pression basse pressostat Cut In Scroll 1 5bar Piston 0 5bar Pression d aspiration S curit Electronique BP S curit M canique BP Pression hau...

Страница 18: ...on 20 Instandhaltung und Wartung 20 Displayanzeige 20 Betriebsparameter 20 Alarm und Fehlermeldungen 21 Reparatur 21 Reglerdefekt 21 Zur cksetzen auf Werkseinstellungen 21 Regleraustausch bei einer Ei...

Страница 19: ...former ab Werk Raumthermostat an diese Klemmen anschlie en Stromversorgung mit Hauptschalter verbinden wie im Schaltplan auf der Innenseite der Frontt r gezeigt Stromversorgung mit Hauptschalter verbi...

Страница 20: ...006 f r 6 00 Uhr W hlen und setzen Sie Parameter t18 Beginn Nacht Stunden z B 022 f r 22 00 Uhr W hlen und setzen Sie Parameter t07 Einstellung Uhr Stunden z B 011 f r 11 xx Uhr W hlen und setzen Sie...

Страница 21: ...Schlie enSiedenVerfl ssigungssatzwiederandieStromversorgungan drehenSiedenGer tehauptschalter in die Ein Position Reglerdefekt F r den Fall dass der Regler ausf llt kann der Verfl ssigungssatz manuell...

Страница 22: ...rehzahlbestimmt Werkseinstellung der Referenz 8 0 K Um auf die Referenz zuzugreifen bet tigen Sie kurz die mittlere Taste am Regler Wenn die Referenz angezeigt wird kann sie ber die obere oder untere...

Страница 23: ...roll 1 4 bar Hubkolbenv 0 4 bar Niederdruckschalter Ein Scroll 1 5 bar Hubkolbenv 0 5 bar Saugdruck Sicherheit Elektronik Niederdr Sicherheit Mechanik Niederdr Hochdruckschalter Ein Scroll und Hubkolb...

Страница 24: ...on 26 Service og vedligeholdelse 26 Hovedvisning 26 Driftsparametre 26 Alarm og fejlmeddelelser 27 Reparation 27 Regulatorfejl 27 Fabriksreset 27 Udskiftning af regulator for et aggregat p stedet 28 R...

Страница 25: ...den midterste knap for at f vist v rdien for det valgte parameter Tryk derefter p den verste eller nederste knap for at indstille v rdien af det valgte parameter Et langt tryk p disse knapper skifter...

Страница 26: ...meter t17 dagstart timer f eks 006 for kl 6 00 V lg og indstil parameter t18 natstart timer f eks 022 for kl 22 00 V lg og indstil parameter t07 indstilling af ur timer f eks 011 for kl 11 xx V lg og...

Страница 27: ...onter den store terminalblok fra regulatoren eller afmonter hele regulatoren Tilslut kondenseringsaggregatet til str mforsyningen igen sl hovedafbryder for hardware til Regulatorfejl hvis regulatoren...

Страница 28: ...or reference 8 0 K Referencen er tilg ngelig ved kort tryk p regulatorens midterste knap N r referencen vises kan den modificeres med verste eller nederste knap Ud over dette kan reguleringen af konde...

Страница 29: ...yk Param c75 Scroll 1 4 bar stempel 0 4 bar Lavtryksafbryder Indkobling Scroll 1 5 bar stempel 0 5 bar Sugetryk Elektronisk sikkerhed LP Mekanisk sikkerhed LP H jtryksafbryder Indkobling Scroll og ste...

Страница 30: ...e speed technology specialists Today we operate from engineering and manufacturing facilities spread across three continents FRCC ES 010 A4 ML October 2014 replace FRCC ES 010 A3 ML July 2014 Copyrigh...

Отзывы: