manualshive.com logo in svg
background image

5

FRCC.EI.019.A2.02 © Danfoss Commercial Compressors 06/12

Instructions

condition during operation.

  •  Never leave the illing cylinder connected to 

the circuit.

9 – Setting the electronic controller

  •  The unit is equipped with an electronic control-

ler which is factory programmed with parame-
ters  for  use  with  the  actual  unit.  Refer  to  Ma-
nual RS8GDxxx for details.

  •  By  default,  the  electronic  controller  display 

shows  the  temperature  value  for  the  suction 
pressure in °C. To show the temperature value 
for  the  condensing  pressure,  push  the  lower 
button (picture 3).

The  electronic  controller  is  factory  preset  for 
operation  with  refrigerant  R404A.  If  another  re-
frigerant is used, the refrigerant setting must be 
changed. Parameter r12 must be set to 0 before 
(software main switch= of).
  •  Push the upper button for a couple of seconds. 

The column with parameter codes appears.

  •  Push the upper or lower button to ind parame-

ter code o30.

  •  Push the middle button until the value for this 

parameter is shown.

  •  Push  the  upper  or  lower  button  to  select  the 

new value: 2 = R22, 3 = R134a, 13 = User dei-
ned, 17 = R507, 19 = R404A, 20 = R407C.

  •  Push the middle button to conirm the selected 

value.

10 – Verification before commissioning

  Use  safety  devices  such  as  safety  pressure 

switch  and  mechanical  relief  valve  in  com-
pliance  with  both  generally  and  locally  appli-
cable  regulations  and  safety  standards.  Ensure 
that they are operational and properly set. 

  Check  that  the  settings  of  high-pressure 

switches and relief valves don’t exceed the maxi-
mum service pressure of any system component.

  •  Verify  that  all  electrical  connections  are  pro-

perly  fastened  and  in  compliance  with  local 
regulations.

  •  When a crankcase heater is required, the unit 

must  be  energized  at  least  12  hours  before 
initial  start-up  and  start-up  after  prolonged 
shutdown for belt type crankcase heaters.

  •  The unit is equipped with a main switch with 

overload  protection.  Overload  protection  is 
preset from factory, but it is recommended to 
check the value before taking the unit in ope-
ration. The  overload  protection  value  can  be 
found in the wiring diagram in the unit front 
door.

11 – Start-up

  •  Never  start  the  unit  when  no  refrigerant  is 

charged.

  •  All service valves must be in the open position.
  •  Check  compliance  between  unit  and  power 

supply.

  •  Check that the crankcase heater is working.
  •  Check that the fan can rotate freely.
  •  Check that the protection sheet has been re-

moved from the backside of condenser.

  •  Balance the HP/LP pressure.
  •  Energize  the  unit.  It  must  start  promptly.  If 

the  compressor  does  not  start,  check  wiring 
conformity and voltage on terminals.

  •  Eventual  reverse  rotation  of  a  3-phase  com-

pressor can be detected by following pheno-
mena; the compressor doesn’t build up pres-
sure, it has abnormally high sound level and 
abnormally low power consumption. In such 
case,  shut  down  the  unit  immediately  and 
connect the phases to their proper terminals.

  •  If the rotation direction is correct the low pres-

sure indication on the controller (or low pres-
sure  gauge)  shall  show  a  declining  pressure 
and the high pressure indication (or high pres-
sure gauge) shall show an increasing pressure.

12 – Check with running unit

  •  Check the fan rotation direction. Air must low 

from the condenser towards the fan.

  •  Check current draw and voltage.
  •  Check  suction  superheat  to  reduce  risk  of 

slugging.

  •  When a sight glass is provided observe the oil 

level at start and during operation to conirm 
that the oil level remains visible.

  •  Respect the operating limits.
  •  Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 
measures such as tube brackets.

  •  When  needed,  additional  refrigerant  in  liquid 

phase may be added in the low-pressure side as 
far as possible from the compressor. The com-
pressor must be operating during this process.

  •  Do not overcharge the system.
  •  Never release refrigerant to atmosphere.
  •  Before  leaving  the  installation  site,  carry  out 

a  general  installation  inspection  regarding 
cleanliness, noise and leak detection.

  •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 
for future inspections.

13 – Emergency running without controller

In case of controller failure, the condensing unit 
can still be operated when the controller stan-
dard wiring (picture 4) is modiied into a tempo-
rary wiring (picture 5) as described below. 

 This modiication may be done by authorized 

electricians only. Country legislations have to be 
followed.

 Disconnect the condensing unit from power 

supply (turn hardware main switch of)
  •  Contact  of  Room  Thermostat  must  be  pos-

sible to switch 250VAC. 

  •  Remove wire 22 (safety input DI3) and wire 24 

(room thermostat DI1) and put them together 

with  an  insulated  250  Vac  10mm²  terminal 
bridge.

  •  Remove  wire  25  (room  thermostat  DI1)  and 

wire  11  (compressor  supply)  and  put  them 
together  with  an  insulated  250VAC  10mm² 
terminal bridge.

  •  H1,  H2,  H3  :  Remove  wire  6  and  connect  it 

with terminal bridge for wire 11 and 25. A fan 
pressure switch or fan speed controller can be 
connected in series to wire 6.

  •  H4 : Remove wire U2 from fan speed control-

ler and connect it with wire 11 and 25.

  •  Remove  wire  14  (crankcase  heater)  and 

connect it to the compressor contactor termi-
nal 22.

  •  Remove  wire  12  (supply  crankcase  heater), 

extend  this  wire  by  using  an  250 Vac  10mm² 
terminal bridge and 1,0mm² brown cable and 
connect it to compressor contactor terminal 21

  •  Remove  the  large  terminal  block  from  the 

controller terminals 10 to 19.

  •  Connect the condensing unit to power supply 

(turn hardware main switch on).

14 – Maintenance

 Always switch of the unit at main switch be-

fore opening the fan door (s).

  Internal  pressure  and  surface  temperature 

are dangerous and may cause permanent injury.
Maintenance  operators  and  installers  require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C and can cause severe burns.

  Ensure  that  periodic  service  inspections  to 

ensure system reliability and as required by local 
regulations are performed.

To  prevent  system  related  problems,  following 
periodic maintenance is recommended:
  •  Verify that safety devices are operational and 

properly set.

  •  Ensure that the system is leak tight.
  •  Check the compressor current draw.
  •  Conirm that the system is operating in a way 

consistent  with  previous  maintenance  re-
cords and ambient conditions.

  •  Check  that  all  electrical  connections  are  still 

adequately fastened.

  •  Keep the unit clean and verify the absence of 

rust  and  oxidation  on  the  unit  components, 
tubes and electrical connections.

The  condenser  must  be  checked  at  least  once 
a  year  for  clogging  and  be  cleaned  if  deemed 
necessary.  Access  to  the  internal  side  of  the 
condenser takes place through the fan door. Mi-
crochannel coils tend to accumulate dirt on the 
surface  rather  than  inside,  which  makes  them 
easier to clean than in-&-tube coils.

  •  Switch of the unit at main switch before ope-

ning the fan door.

  •  Remove  surface  dirt,  leaves,  ibres,  etc.  with 

Содержание OP-LPHM018-026

Страница 1: ...1 FRCC EI 019 A2 ML Danfoss Commercial Compressors 06 12 Instructions OP LPHM018 026 OP MPHM007 010 012 015 018 OP LPHM048 068 OP MPHM026 034 OP MPUM034 046 OP MPGM034 ...

Страница 2: ...P VIEW 966 UNIT HEIGHT FRONT VIEW 35 SWITCH HEIGHT MOUNTING Ø12 HOLE FOR SIGHT 50 TYP DISPLAY CONTROLLER PORTS CABLE ENTRY LIQUID PORT SUCTION PORT MCHX RH VIEW BACK VIEW ISO VIEW LH VIEW 479 MOUNTING C C 80 GLASS 1702 MOUNTING C C OP LPHM215 271 OP MPUM125 162 Instructions OP LPHM096 136 OP MPUM068 080 107 ...

Страница 3: ...se instructions and sound refrigeration engineering practice relating to installation commissioning maintenance and service A Model B Code number C Refrigerant D Supply voltage Locked Rotor Ampere Maxi mum Current Consumption E Application F Protection G Housing Service Pressure H Serial Number and bar code I Mounting holes for stack mounting J Electronic controller display K Main switch L Cable e...

Страница 4: ... in picture 2 Slowly release the nitrogen holding charge through the schrader port Connect the unit to the system as soon as pos sible to avoid oil contamination from ambient moisture Avoid material entering into the system while cutting tubes Never drill holes where burrs cannot be removed Braze with great care using state of the art technique and vent piping with nitrogen gas low Connect the req...

Страница 5: ...s is provided observe the oil level at start and during operation to conirm that the oil level remains visible Respect the operating limits Check all tubes for abnormal vibration Move ments in excess of 1 5 mm require corrective measures such as tube brackets When needed additional refrigerant in liquid phase may be added in the low pressure side as far as possible from the compressor The com pres...

Страница 6: ...stle Do not use a wire brush Do not impact or scrape the coil with the vacuum tube or air nozzle Before closing the fan door turn the fan blade in the position shown in picture 6 to avoid that the door hits the fan If the refrigerant system has been opened the system has to be lushed with dry air or nitrogen to remove moisture and a new ilter drier has to be installed If evacuation of refrigerant ...

Страница 7: ...at optional X1 Terminal Supply Supply Fan Fan Alarm Alarm Comp Compressor CCH Crankcase Heater Aux Auxiliary P U B1 P U B2 T S1 M 1 M2 R5 P B4 P B3 K2 F1 N L1 I I I 2 4 6 Q1 COM NC NO K2 C1 C2 M 1 M1 K1 R1 R2 R3 C3 WD2 DI1 DI2 S1 S2 S3 S4 S5 AO1 Display EKA S6 s Alarm Comp Fan CCH AUX 230Vac 230Vac L L N PE PE DI3 230Vac out Supply Fan Optyma Plus Controller RS485 A B A1 R4 Code G OP LPHM026 048 0...

Страница 8: ...Plus Controller RS485 A B A1 M 1 M2 M 1 M3 C3 C4 L1 L2 L2 N N X1 S2 0 10V U L N A2 A1 Optyma Plus Controller A2 Fan Speed Controller B1 Condensing Pressure Transducer B2 Suction Pressure Transducer B3 High Pressure Switch B4 Low Pressure Switch C3 Run Capacitor Fan 1 C4 Run Capacitor Fan 2 F1 Fuse Control Circuit K2 Contactor M1 Compressor M2 Fan Motor 1 M3 Fan Motor 2 Q1 Main Switch R1 Ambient Te...

Отзывы: