Danfoss Old ICAD 600 series Скачать руководство пользователя страница 2

Valve label ID:

4

5

Valve size setup (mandatory)

Programming the ICAD

Changing analogue input signal (optional)

Decrease 

value

Edit /

Enter

Increase

value

Hold down   for 

2 seconds to enter 
programming mode.

; 01

; 10

Press   and 

go to parameter 10.
Press 

Press   until 

you reach 11 (pass-
word). Press   

Press   until 

you reach parameter 26
Press   

11

; 26

Press   or   

to select ICM size.
Press   

ICM / ICAD is now 
calibrating.

0

; 26

CA

Hold down   for 

2 seconds to exit 
programming mode.

1: ICM 20 with ICAD 600 
2: ICM 25 with ICAD 600 
3: ICM 32 with ICAD 600 
4: ICM 40 with ICAD 900/1200 
5: ICM 50 with ICAD 900/1200 

; 01

Hold down   for 

2 seconds to enter 
programming mode.

; 03

Press   until you 

reach parameter 03. 
Press   

Press   or   

to select analogue
input signal.

1: 0-20 mA 
2: 4-20 mA* 
3: 0-10 V 
4: 2-10 V

2

; 03

Press   

A3

If A3 alarm occurs 
the analogue input 
signal is out of range.

For further functions, 
programming possibilities 
and factory settings; 
please see ICAD instruction.

24 Volt d.c. ONLY

DKRCI.PI.HV0.J2.02 / 520H4887 / 027R9801

 

©

 Danfoss A/S (AC-SMC/MWA), 05 - 2011

Note:
If the keypad is not operated within 20 seconds; 
time out will automatically exit programming mode.

Hold down   for 

2 seconds to exit 
programming mode.

* default factory setting

; 03

ICM 20

ICM 25-65

ICM 100-150

6: ICM 65 with ICAD 900/1200 
7: ICM 100 with ICAD 1200 
8: ICM 125 with ICAD 1200 
9: ICM 150 with ICAD 1200

When powering up the ICAD, A1 will flash in the display

Factory reset of ICAD

Disconnect power 

Press down   and   

 

simultaneously while 
reconnecting power 

Release    and   

Note: 
If factory reset has been performed the 
ICAD will start flashing A1 in the display.