Installation

Use

ICAD 600, ICAD 900 and ICAD 1200 can be 

used  together with the following Danfoss 

valves (fig. 1, 5a and 5b).

Electrical data

Supply voltage is galvanically isolated from 

in-/output.

Supply voltage

24 V d.c., +10% / -15%

Load  ICAD 600: 1.2 A

 

ICAD 900: 2.0 A

 

ICAD 1200: 3.0 A

Fail safe supply

Min. 19 V d.c.

Load  ICAD 600: 1.2 A

 

ICAD 900: 2.0 A

 

ICAD 1200: 3.0 A

Anolog Input - Current or Voltage

Current

0/4 - 20 mA

Load: 200 

W

Voltage

0/2 - 10 V d.c.

Load: 10 k

W

Analog Output

0/4 - 20 mA

Load: ≤ 250 

W

Digital Input - Digital ON/OFF input by means 

of voltfree contact (Signal/Telecom relays 

with gold-plated contacts recommended) – 

Voltage input used

ON:  Contact impedance < 50 

W

)

OFF: Contact impedance > 100 k

W

Digital Output - 3 pcs. NPN transistor output

External supply:  5 - 24 V d.c. (same supply 

as for ICAD can be used, 

but please note that the 

galvanically isolated 

system will then be 

spoiled).

Output load: 

50 

W

Load: 

Max. 50 mA

Temperature range (ambient)

–30°C/+50°C (–22°F/122°F)

Enclosure

IP 67 (~NEMA 6)

ENGLISH

Electrical connection

Connection to ICAD is done via M12 

connectors. ICAD has two M12 male 

connectors build-in:

Power supply: 4 poled M12 male connector

Control signals: 8 poled M12 male connector
If ICAD is delivered with cables (1.5 m. (60 

in.)) M12 female connectors: (Cable set with 

M12 female connectors in other lengths are 

available)

Power Supply cable with 4 poled M12 

female connector

3 x 0.34 mm

2

 (3 x ~22 AWG) (fig. 6)

  I:  Black  (+)  19 - 24 V d.c. fail safe 

     

 

supply (optional).

  II:  White  (+)  24 V d.c.

  III:  Brown  (–)  24 V d.c.

 

Control cable with 8 poled M12 

female connector

7 x 0.25 mm

2

 (7 x ~24 AWG) (fig. 7)

  A:  Black  (–)  Digital output. 

     

 

Common Alarm.

  B:  Brown  (–)  Digital output.

     

 

ICM fully open.

  C:  Red 

(–)  Digital output.

     

 

ICM fully closed.

  D:  Orange (–)  GND - Ground.

  E:   Yellow  (+)  Analog input  

     

 

0/4-20 mA. *)

  F:   Green   (+)  Analog input 0/2-10 V /  

     

 

DI1 - Digital ON/OFF  

    

  input. 

  G:  Blue   (+)  Analog output  

     

 

0/4-20 mA. *)

  *)  If Neutral zone / 3 point control is 

    selected (parameter i02 = 3) then  

    E and G is used as DI2 - Digital  

    ON/OFF input. Se fig. 9.

Electrical installation

General procedure for ICAD 600/900/1200 

installed on all ICM valves.
All necessary electrical connections to be 

made. Analog or digital operation of ICM 

valve.

Fig. 6

Analog operation

 - 7 wired cable (A-G) 

Modulation control. ICM valve to be 

controlled from Danfoss electronics, 

type EKC (fig. 7), or third party 

electronics (like e.g. PLC).

Connect analog input signals. Currrent 

(mA) or Voltage (V). See 

Parameter 

list

 for configuration of analog input 

signals.

Yellow (+) and Orange (GND) are used 

for current (mA) input.

 or

Green (+) and Orange (GND) are used 

for Voltage (V) input.

Blue (+) and Orange (GND) are used 

for current (mA) output (optional, not 

mandatory).

 

Fig. 6

Digital operation

 - 7 wired cable (A-G) 

ON/OFF ICM solenoid valve operation. 

ICM valve to be controlled by means of 

a digital voltfree contact.

Connect digital input signals (fig. 8). 

See 

Parameter list

 for configuration 

of digital input signals.

Green (+) and Orange (GND) are 

connected to a voltfree contact.

Digital output signals are optional, not 

mandatory.

Black (–) and Orange (GND) are 

connected to auxiliary relay for 

Common Alarm.

Brown (–) and Orange (GND) are 

connected to an auxiliary relay 

indicating ICM fully open.

Red (–) and Orange (GND) are 

connected to an auxiliary relay 

indicating ICM fully closed.

Supply voltage

 - 3 wired cable (I, II, III) 

ICAD must be connected to a normal  

24 V d.c. supply. As an option, a fail safe 

supply is possible by means of a battery 

or UPS (Uninterruptible Power Supply). 

When voltage is applied as described 

below, ICAD is ready to be configurated. 

See 

Parameter list

ICAD configuration can be done 

independently whether the ICAD is 

installed on the ICM valve or not. 

See 

Mechanical installation

.

Connect the White (+) and Brown (–) 

to a 24 V d.c. supply voltage (fig. 6).

Fail safe supply as an option (not 

mandatory).

Connect the Black (+) and Brown (–) to 

a fail safe supply.

Mechanical installation

General procedure for ICAD 600/900/1200 

installed on all ICM valves (fig. 3).

Check that the three socket set screws 

are fully unscrewed counter clockwise 

with a 2.5 mm Hexagon key.
Mount ICAD by slowly lowering it on 

top of the ICM valve.
The magnet coupling will drag the ICM 

and ICAD together and in position.
Push ICAD in place.
Fasten ICM and ICAD with the three 

socket set screws using a 2.5 mm 

Hexagon key.

Neutral zone / 3 point control (fig. 9)

¡02

 = 3 

When 

¡02

 = 3 the speed given by 

¡04

 

(opening) and i14 (closing) are active

When 

¡02

 = 3 the factory setting of  

¡04

 

(opening) and 

¡14

 (closing) are both set to 

10.

¡13

 (Inverse operation) is active

¡16

 = 1 (Encoder operation enable) is active.

¡13

 = 0 (Direct operation) 

DI1 = DI2 = OFF 

ICAD/ICM maintain current position

DI1 = DI2 = ON 

ICAD/ICM  maintain current position

DI1 = ON, DI2 = OFF

ICAD increase opening degree

DI1 = OFF, DI2 = ON

ICAD decrease opening degree

¡13

 = 1 (Inverse operation) 

DI1 = DI2 = OFF 

ICAD maintain current position

DI1 = DI2=ON 

ICAD maintain current position

DI1 = ON, DI2 = OFF

ICAD decrease opening degree

DI1 = OFF, DI2 = ON

ICAD increase opening degree

Do not instal ICAD must before 

welding. This apply for electrical as 

well as for mechanical installation.

Please observe that ICAD when 

connected to 24 V d.c.,  will send 

out acoustic noise at stand still.  This 

has no influence on the function/

operation of the ICAD.

ICAD 600

ICAD 900

ICAD 1200

ICM 20

ICM 40

ICM 40

ICM 25

ICM 50

ICM 50

ICM 32

ICM 65

ICM 65
ICM 100
ICM 125
ICM 150

Special moisture seal is damaged if 

screws are removed (fig. 3, pos. A)

Содержание Old ICAD 1200 series

Страница 1: ...027R9796 Fig 1 Fig 2 Fig 3 Fig 4 ICAD 600 ICAD 900 ICAD 600 ICAD 900 ICAD 1200 Fig 5a ICM ICAD 600 Fig 5b ICM ICAD 900 mm in H 45 1 77 L3 25 1 Instruction Actuator ICAD 600 ICAD 900 ICAD 1200 ICAD 1200 Fig 5c ICM ICAD 1200 Note When mounting the ICAD make sure to push ICAD down to mechanical stop ...

Страница 2: ...safe supply Battery UPS 19 V d c II White Supply voltage 24 V d c III Brown Digital Ouput Analog In Output ICAD 600 900 1200 Uninterruptible Power Supply Terminal box Control cable Supply cable Only possible with EKC 347 Terminal box ICAD 600 900 1200 Digital I O for ON OFF valve operation Auxiliary relays Terminal box Fig 8 III I II C D E B A G F 4 pin male connector 8 pin male connector External...

Страница 3: ...d Orange GND are used for current mA output optional not mandatory Fig 6 Digital operation 7 wired cable A G ON OFF ICM solenoid valve operation ICM valve to be controlled by means of a digital voltfree contact Connect digital input signals fig 8 See Parameter list for configuration of digital input signals Green and Orange GND are connected to a voltfree contact Digital output signals are optiona...

Страница 4: ...lve with low speed according to a digital input signal Med represents that ICAD is operating the ICM valve like an ON OFF solenoid valve with medium speed according to a digital input signal High represents that ICAD is operating the ICM valve like an ON OFF solenoid valve with high speed according to a digital input signal Like below Alarms ICAD can handle and display different alarms Description...

Страница 5: ...ve 2 Open Valve 3 Maintain valve position 4 Go to OD given by 12 Fail safe supply 08 0 1 0 Yes Fail safe supply connected and enable of A4 alarm 0 No 1 Yes DI function 09 1 2 1 No Define function when DI is ON short circuited DI terminals when 02 2 1 Open ICM valve DI OFF Close ICM valve 2 Close ICM valve DI OFF Open ICM valve Password 10 0 199 0 Enter number to access password protected parameter...

Страница 6: ... DI2 OFF 01 DI1 OFF DI2 ON 11 DI1 ON DI2 ON DO Close 55 0 1 DO Closed status ON when OD 3 DO Open 56 0 1 DO Open status ON when OD 97 DO Alarm 57 0 1 DO alarm status ON when a Alarm is detected Display mP SW ver 58 0 100 Software version for display microprocessor Motor mP SW ver 59 0 100 Software version for motor microprocessor Reset to factory setting 1 Remove the power supply 2 Activate down a...

Страница 7: ......

Страница 8: ... Danfoss A S AC SMC MWA 08 2011 DKRCI PI HV0 E6 02 520H3832 8 www danfoss com icv ...

Отзывы: