23
VLT is a registered Danfoss trade mark
MG.10.P2.22
Message
Translation
Examples
(continued)
EXAMPLE SIX: Write Parameter 533,
Display Text 1, (VLT 6000 only) with
“1234567890” (Data Type 9 – Text String).
Write IND with “0500” to perform a text
write.
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Slave
Address
Function
Register
Addr HI
Register
Addr LO
Preset Data
HI
Preset Data
LO
Error Check
01
06
00
00
05
00
--
Message sent to Modbus master from Modbus option card
Message sent to Modbus master from Modbus option card
Message sent to Modbus master from Modbus option card
Message sent to Modbus master from Modbus option card
Message sent to Modbus master from Modbus option card
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Slave
Address
Function
Register
Addr HI
Register
Addr LO
Preset Data
HI
Preset Data
LO
Error Check
01
06
00
00
05
00
--
Commands Modbus to text mode.
Message sent to Modbus RTU option card from Modbus master
Message sent to Modbus RTU option card from Modbus master
Message sent to Modbus RTU option card from Modbus master
Message sent to Modbus RTU option card from Modbus master
Message sent to Modbus RTU option card from Modbus master
Modbus Function 06
HEX
Preset Single Register
Message sent to Modbus RTU option card from Modbus master
Message sent to Modbus RTU option card from Modbus master
Message sent to Modbus RTU option card from Modbus master
Message sent to Modbus RTU option card from Modbus master
Message sent to Modbus RTU option card from Modbus master
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Slave
Address
Function
Start Addr HI
Start Addr L
No. of
Registers HI
No. of
Registers LO
Byte Count
Data HI
(Reg 414D2)
01
10
14
D1
00
05
0A
31
Byte 8
Byte 9
Byte 10
Byte 11
Byte 12
Byte 13
Byte 14
Byte 15
Data HI
(Reg 414D2)
Data HI
(Reg 414D3)
Data HI
(Reg 414D3)
Data HI
(Reg 414D4)
Data HI
(Reg 414D4)
Data HI
(Reg 414D5)
Data HI
(Reg 414D5)
Data HI
(Reg 414D6)
32
33
34
35
36
37
38
39
Byte 16
Byte 17
Data HI
(Reg 414D6)
Error Check
30
--
Message sent to Modbus master from Modbus RTU option card
Message sent to Modbus master from Modbus RTU option card
Message sent to Modbus master from Modbus RTU option card
Message sent to Modbus master from Modbus RTU option card
Message sent to Modbus master from Modbus RTU option card
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Slave
Address
Function
Start Addr HI
Start Addr LO
No. Registers
HI
No. Registers
LO
Error Check
01
10
14
D1
00
05
--
All values are in hexadecimal.
Modbus Function 10
HEX
Preset Multiple Registers